Checking and setting the Free time
The duration for which the discharge monitor is suppressed after activating the
’Unlimited’ key can be set from one to eight hours from the front panel.
Checking the Free time
1. Depress ’Unlimited’ key for 5 seconds until a series of short beeps begins.
2. Release the key, and all indicators turn green
3. A short beep now sounds for each hour of suppression duration
4. The system reverts to normal operation.
Example:
Green indicators and 3 short beeps (three hours)
Discharge monitor is suppressed for three hours by activation of ’Unlimited’’.
Setting the Free time
1. Depress ’Unlimited’ key for 5 seconds until a series of short beeps begins.
2. While system beeps, release the key briefly, and depress again for 5 seconds.
3. Upper indicator turns green; Free time setting must commence within 6 seconds.
(The green light progresses down one indicator every second).
4. Press ’Unlimited’ once for each hour of desired Free time.
5. Next, let the green light progress through the bottom indicator
6. The system reverts to normal operation..