7-12 Adaptive Control Gain-2
Range:
Function:
75%
*
[1–200%] Adjusts the performance of adaptive control.
The setting affects both starting and stopping
control.
NOTICE
Leave the gain setting at the default
level unless adaptive control
performance is not satisfactory.
If the motor accelerates or decelerates
quickly at the end of a start or stop,
increase the gain setting by 5–10%. If
the motor speed fluctuates during
starting or stopping, decrease the gain
setting slightly.
7-13 Adaptive Start Profile-2
Option:
Function:
Selects which profile the soft starter
uses for an adaptive control soft start.
Early acceleration
Constant acceleration*
Late acceleration
7-14 Adaptive Stop Profile-2
Option:
Function:
Selects which profile the soft starter
uses for an adaptive control soft stop.
Early deceleration
Constant deceleration*
Late acceleration
7-15 Brake Torque-2
Range:
Function:
20%
*
[20–100%] Sets the amount of brake torque the soft
starter uses to slow the motor.
7-16 Brake Time-2
Range:
Function:
1 s
*
[1–30 s]
NOTICE
This parameter is used with
parameter
7-11 Stop Time-2
.
Sets the duration for DC injection during a
braking stop.
8.8 Display
8-1 Language
Option:
Function:
Selects in which language the LCP
shows messages and feedback.
English*
Chinese (
中丈
)
Spanish (Español)
German (Deutsch)
Portuguese (Português)
8-1 Language
Option:
Function:
French (Français)
Italian (Italiano)
Russian (
Русский
)
8.8.1 User-programmable Screen
Selects which 4 items to show on the programmable
monitoring screen.
8-2 User Screen - Top Left
Option:
Function:
Selects the item shown in the top left part of
the screen.
Blank
Shows no data in the selected area, allowing
long messages to be shown without
overlapping.
Starter state
The operating state of the soft starter (starting,
running, stopping, or tripped). Only available
for
Top L
and
Btm L
.
Motor current
The average current measured on 3 phases.
Motor pf*
The motor power factor measured by the soft
starter.
Mains
frequency
The average frequency measured on 3 phases.
Motor kW
The motor running power in kW.
Motor hp
The motor running power in horse power.
Motor temp
The motor temperature, calculated by the
thermal model.
kWh
The number of kWh the motor has run via the
soft starter.
Hours run
The number of hours the motor has run via
the soft starter.
8-3 User Screen - Top Right
Option:
Function:
Selects the item shown in the top right part of
the screen.
Blank*
Shows no data in the selected area, allowing
long messages to be shown without
overlapping.
Starter state
The operating state of the soft starter (starting,
running, stopping, or tripped). Only available
for
Top L
and
Btm L
.
Motor current
The average current measured on 3 phases.
Motor pf
The motor power factor measured by the soft
starter.
Mains
frequency
The average frequency measured on 3 phases.
Motor kW
The motor running power in kW.
Motor hp
The motor running power in horse power.
Motor temp
The motor temperature, calculated by the
thermal model.
Parameter Descriptions
VLT
®
Soft Starter MCD 500
68
Danfoss A/S © 05/2016 All rights reserved.
MG17K602
8
8