![Danfoss vlt soft starter mcd 500 Operating Manual Download Page 85](http://html1.mh-extra.com/html/danfoss/vlt-soft-starter-mcd-500/vlt-soft-starter-mcd-500_operating-manual_3880698085.webp)
Environmental
Protection
MCD5-0021B to MCD5-0105B
IP20 & NEMA, UL Indoor Type 1
MCD5-0131B to MCD5-1600C
IP00, UL Indoor Open Type
Operating temperature
-10
°
C (14
°
F) to +60
°
C (140
°
F), above 40
°
C (104
°
F) with derating
Storage temperature
-25
°
C (-13
°
F) to +60
°
C
Operating altitude (using MCD PC software)
0–1000 m (0–3281 ft), above 1000 m (3281 ft) with derating
Humidity
5–95% relative humidity
Pollution degree
Pollution degree 3
Vibration
IEC 60068-2-6
Heat dissipation
During start
4.5 W per ampere
During run
MCD5-0021B to MCD5-0053B
≤
39 W approximately
MCD5-0068B to MCD5-0105B
≤
51 W approximately
MCD5-0131B to MCD5-0215B
≤
120 W approximately
MCD5-0245B to MCD5-0469B
≤
140 W approximately
MCD5-0525B to MCD5-0961B
≤
357 W approximately
MCD5-0245C to MCD5-0927C
4.5 W per ampere approximately
MCD5-1200C to MCD5-1600C
4.5 W per ampere approximately
Certification
C
✓
IEC 60947-4-2
UL/C-UL
MCD5-0021B to MCD5-0396B, MCD5-0245C to MCD5-1600C
MCD5-0469B to MCD5-0961B
MCD5-0021B to MCD5-105B
MCD5-0131B to MCD5-1600C
UL 508
1)
UL-listed
UL-recognized
IP20, when fitted with optional finger guard kit
CE
IEC 60947-4-2
CCC
GB 14048-6
Marine
(MCD5-0021B to MCD5-0961B)
Lloyds Marine No 1 Specification
RoHS
Compliant with EU Directive 2002/95/EC
1) For UL certification extra requirements may apply, depending on the models. For details, see chapter 11.1 UL-compliant Instal-
lation.
11.1 UL-compliant Installation
This section details more requirements and configuration
settings for the VLT
®
Soft Starter MCD 500 to be UL-
compliant. See also
.
11.1.1 Models MCD5-0021B to
MCD5-0105B
There are no additional requirements for these models.
11.1.2 Models MCD5-0131B to
MCD5-0215B
•
Use with finger guard kit, ordering number
175G5662.
•
Use the recommended pressure terminal/
connector kit. See
for more
information.
11.1.3 Models MCD5-0245B to
MCD5-0396B
•
Use with finger guard kit, ordering number
175G5730.
•
Use the recommended pressure terminal/
connector kit. See
for more
information.
11.1.4 Models MCD5-0245C
•
Use the recommended pressure terminal/
connector kit. See
for more
information.
Specifications
Operating Guide
MG17K602
Danfoss A/S © 05/2016 All rights reserved.
83
11
11