4.4.3 Inside Delta Connection (Bypassed)
NOTICE
Models MCD5-0021B to MCD5-0961B are internally bypassed. Models MCD5-0245C to MCD5-1600C require an external
bypass contactor.
Type code
Ampere ratings A]
AC-53b
3-30:330
AC-53b
4.20-:340
AC-53b
4.5-30:330
MCD5-0021B
32
26
22
MCD5-0037B
56
47
39
MCD5-0043B
65
56
45
MCD5-0053B
80
69
55
AC-53b
3-30:570
AC-53b
4-20:580
AC-53b
4.5-30:570
MCD5-0068B
102
83
71
MCD5-0084B
126
104
87
MCD5-0089B
134
112
92
MCD5-0105B
158
143
117
MCD5-0131B
197
159
136
MCD5-0141B
212
181
146
MCD5-0195B
293
241
201
MCD5-0215B
323
268
223
MCD5-0245B
368
291
254
MCD5-0245C
383
302
264
MCD5-0331B
497
400
343
MCD5-0360C
540
465
395
MCD5-0380C
570
539
449
MCD5-0396B
594
478
410
MCD5-0428C
645
552
463
MCD5-0469B
704
575
490
MCD5-0525B
787
637
546
MCD5-0595C
930
810
651
MCD5-0619C
975
842
683
MCD5-0632B
948
768
658
MCD5-0790C
1185
1072
869
MCD5-0744B
1116
910
774
MCD5-0826B
1239
1026
857
MCD5-0927C
1395
1244
992
MCD5-0961B
1441
1194
997
MCD5-1200C
1800
1800
1607
MCD5-1410C
2115
1979
1671
MCD5-1600C
2400
2400
2030
Table 4.4 Bypassed Models