6-23 Terminal 60 High Current
Range:
Function:
[0.01 - 20.00 mA]
Normally (default) set to 20 mA.
6-24 Terminal 60 Low Feedback Value
Range:
Function:
[-4999 - 4999] Value corresponding to
setting.
6-25 Terminal 60 High Feedback Value
Range:
Function:
[-4999 - 4999] Value corresponding to
setting.
6-26 Terminal 60 Filter Time Constant
Range:
Function:
[0.01 - 10.00 s]
Filter for suppressing electrical noise.
7-20 Process CL Feedback Resource
Range:
Function:
[]
Choose [2] analog input 60.
7-30 Process PI Normal/Inverse
Range:
Function:
[]
Most PI controllers are “Normal”.
7-31 Process PI Anti Windup
Range:
Function:
[]
Leave
Enabled
normally.
7-32 Process PI Start Speed
Range:
Function:
[0.0 - 200.0 Hz]
Choose expected normal running speed.
7-33 Process PI Proportional Gain
Range:
Function:
[0.00 - 10.00]
Enter the P-factor.
7-34 Process PI Integral Time
Range:
Function:
[0.10 - 9999.00 s]
Enter the I-factor.
7-38 Process Feed Forward Factor
Range:
Function:
[0 - 400%]
Only applicable with changing set-points.
7.5 Main Menu
7.5.1 Main Menu
[Main Menu] is used for programming all parameters. The
Main Menu parameters can be accessed immediately
unless a password has been created via
0-60 Main Menu
Password
. For the majority of VLT
®
Micro Drive FC 51
applications it is not necessary to access the Main Menu
parameters but instead the Quick Menu provides the
simplest and quickest access to the typical required
parameters.
The Main Menu accesses all parameters.
1.
Press [MENU] key until indicator in display is
placed above “Main Menu”.
2.
Use [
▲
] [
▼
] to browse through the parameter
groups.
3.
Press [OK] to select a parameter group.
4.
Use [
▲
] [
▼
] to browse through the parameters in
the specific group.
5.
Press [OK] to select the parameter.
6.
Use [
▲
] [
▼
] to set/change the parameter value.
[BACK] is used to go one level back.
Programming
VLT Micro Drive Design Guide
MG02K102 - VLT
®
is a registered Danfoss trademark
67