NOTE
Parameter 6-19 must be set according to Switch 4 position.
6.16 Final Set-Up and Test
To test the set-up and ensure that the frequency converter
is running, follow these steps.
Step 1. Locate the motor name plate
The motor is either star- (Y) or delta- connected (
Δ
). This
information is located on the motor name plate data.
Step 2. Enter the motor name plate data in this parameter
list.
To access this list first press the [QUICK MENU] key then
select “Q2 Quick Setup”.
1.
Motor Power [kW]
or Motor Power [HP]
1-20 Motor Power [kW]
1-21 Motor Power [HP]
2.
Motor Voltage
1-22 Motor Voltage
3.
Motor Frequency
1-23 Motor Frequency
4.
Motor Current
1-24 Motor Current
5.
Motor Nominal Speed
1-25 Motor Nominal
Speed
3~ MOTOR NR. 1827421 2003
S/E005A9
1,5
KW
n2 31,5
/min.
400
Y
V
n1 1400
/min.
50
Hz
COS
0,80
3,6
A
1,7L
B
IP 65
H1/1A
BAUER D-7 3734 ESLINGEN
130B
T307.10
Step 3. Activate the Automatic Motor Tuning (AMT)
Performing an AMT will ensure optimum performance. The
AMT measures the values from the motor model
equivalent diagram.
1.
Connect terminal 27 to terminal 12 or set
5-12 Terminal 27 Digital Input
to 'No function'
(
5-12 Terminal 27 Digital Input
[0])
2.
Activate the AMT
1-29 Automatic Motor
Adaptation (AMA)
.
3.
Choose between complete or reduced AMT. If an
LC filter is mounted, run only the reduced AMT,
or remove the LC filter during the AMT
procedure.
4.
Press the [OK] key. The display shows “Press
[Hand on] to start”.
5.
Press the [Hand on] key. A progress bar indicates
if the AMT is in progress.
Stop the AMT during operation
1.
Press the [OFF] key - the frequency converter
enters into alarm mode and the display shows
that the AMT was terminated by the user.
How to Install
VLT Micro Drive Design Guide
58