6.14 Control Terminals
6.14.1 Access to Control Terminals
All control cable terminals are located underneath the
terminal cover in front of the frequency converter. Remove
the terminal cover using a screwdriver.
Illustration 6.11 Removing terminal cover
NOTE
See back of terminal cover for outlines of control terminals
and switches.
6.14.2 Connecting to Control Terminals
shows all control terminals of the frequency
converter. Applying Start (term. 18) and an analog
reference (term. 53 or 60) make the frequency converter
run.
Illustration 6.12 Overview of control terminals in PNP-configu-
ration and factory setting.
6.15 Switches
NOTE
Do not operate switches with power on the frequency
converter.
Bus termination:
Switch
BUS TER
pos. ON terminates the RS485 port,
terminals 68, 69. See
.
Default setting = Off.
Illustration 6.13 S640 Bus termination
S200 Switches 1-4:
Switch 1:
*OFF = PNP terminals 29
ON = NPN terminals 29
Switch 2:
*OFF = PNP terminal 18, 19, 27 and 33
ON = NPN terminal 18, 19, 27 and 33
Switch 3:
No function
Switch 4:
*OFF = Terminal 53 0 - 10 V
ON = Terminal 53 0/4 - 20 mA
* = default setting
Table 6.5 Settings for S200 Switches 1-4
Illustration 6.14 S200 Switches 1-4.