FC 51
UL
Max. fuses non UL
Bussmann
Bussmann
Bussmann
Littel fuse
Ferraz-
Shawmut
Ferraz-
Shawmut
1 X 200-240 V
kW
Type RK1
Type J
Type T
Type RK1
Type CC
Type RK1
Type gG
0K18 - 0K37
KTN-R15
JKS-15
JJN-15
KLN-R15
ATM-R15
A2K-15R
15A
0K75
KTN-R25
JKS-25
JJN-25
KLN-R25
ATM-R25
A2K-25R
25A
1K5
KTN-R35
JKS-35
JJN-35
KLN-R35
-
A2K-35R
35A
2K2
KTN-R45
JKS-45
JJN-45
KLN-R45
-
A2K-45R
45A
3 x 200-240 V
0K25
KTN-R10
JKS-10
JJN-10
KLN-R10
ATM-R10
A2K-10R
10A
0K37
KTN-R15
JKS-15
JJN-15
KLN-R15
ATM-R15
A2K-15R
15A
0K75
KTN-R20
JKS-20
JJN-20
KLN-R20
ATM-R20
A2K-20R
20A
1K5
KTN-R25
JKS-25
JJN-25
KLN-R25
ATM-R25
A2K-25R
25A
2K2
KTN-R40
JKS-40
JJN-40
KLN-R40
ATM-R40
A2K-40R
40A
3K7
KTN-R40
JKS-40
JJN-40
KLN-R40
-
A2K-40R
40A
3 x 380-480 V
0K37 - 0K75
KTS-R10
JKS-10
JJS-10
KLS-R10
ATM-R10
A6K-10R
10A
1K5
KTS-R15
JKS-15
JJS-15
KLS-R15
ATM-R15
A2K-15R
15A
2K2
KTS-R20
JKS-20
JJS-20
KLS-R20
ATM-R20
A6K-20R
20A
3K0
KTS-R40
JKS-40
JJS-40
KLS-R40
ATM-R40
A6K405R
40A
4K0
KTS-R40
JKS-40
JJS-40
KLS-R40
ATM-R40
A6K-40R
40A
5K5
KTS-R40
JKS-40
JJS-40
KLS-R40
-
A6K-40R
40A
7K5
KTS-R40
JKS-40
JJS-40
KLS-R40
-
A6K-40R
40A
Table 3.3: Fuses
3.1.3 EMC-Correct Installation
Following these guidelines is advised, where compliance with EN 61000-6-3/4, EN 55011 or EN 61800-3
First environment
is required. If the installation
is in EN 61800-3
Second environment
, then it is acceptable to deviate from these guidelines. It is however not recommended.
Good engineering practice to ensure EMC-correct electrical installation:
•
Use only braided screened/armoured motor cables and control cables.
The screen should provide a minimum coverage of 80%.The screen material must be metal, not limited to but typically copper, aluminium, steel
or lead. There are no special requirements for the mains cable.
•
Installations using rigid metal conduits are not required to use screened cable, but the motor cable must be installed in conduit separate from
the control and mains cables. Full connection of the conduit from the drive to the motor is required. The EMC performance of flexible conduits
varies a lot and information from the manufacturer must be obtained.
•
Connect the screen/armour/conduit to earth at both ends for motor cables and control cables.
•
Avoid terminating the screen/armour with twisted ends (pigtails). Such a termination increases the high frequency impedance of the screen,
which reduces its effectiveness at high frequencies. Use low impedance cable clamps or glands instead.
•
Ensure good electrical contact between the de-coupling plate and the metal chassis of the frequency converter, see Instruction MI.02.BX.YY.
•
Avoid using unscreened/unarmoured motor or control cables inside cabinets housing the drive(s), where possible.
3.2 Mains Connection
3.2.1 Connecting to Mains
Step 1: First mount earth cable.
Step 2: Mount wires in terminals L1/L, L2 and L3/N and tighten.
Illustration 3.1: Mounting of earth cable and mains wires.