12-06 Name Servers
Range:
Function:
0
*
[0 - 2147483647 ] IP addresses of Domain Name Servers.
Can be automatically assigned when
using DHCP.
12-07 Domain Name
Range:
Function:
0 [0 - 2147483647 ] Domain name of the attached network.
Can be automatically assigned when
using DHCP.
12-08 Host Name
Range:
Function:
Blank
[0-19 characters]
Logical (given) name of option.
12-09 Physical Address
Range:
Function:
0
*
[0 - 0 ] Read only Displays the Physical (MAC) address of
the option.
6.2.2 12-1* Ethernet Link Parameters
12-1* Ethernet Link parameters
Option:
Function:
Applies for whole parameter group.
[0]
Port 1
[1]
Port 2
12-10 Link Status
Option:
Function:
12-11 Link Duration
Range:
Function:
Application dependent
*
[Application dependant]
12-12 Auto Negotiation
Option: Function:
Configures Auto Negotiation of Ethernet link
parameters, for each port: ON or OFF.
[0] Off
Link Speed
and
Link Duplex
can be configured in
12-13 Link Speed
and
.
[1] On
12-13 Link Speed
Option:
Function:
Forces the link speed for each port in 10 or 100
Mbps. If
12-12 Auto Negotiation
is set to: ON,
this parameter is read only and displays the
actual link speed. “None” is displayed if no link
is present.
[0]
*
None
[1]
10 Mbps
[2]
100 Mbps
12-14 Link Duplex
Option:
Function:
Forces the duplex for each port to Full or Half
duplex. If
12-12 Auto Negotiation
is set to: ON,
this parameter is read only.
[0]
Half Duplex
[1]
*
Full Duplex
6.2.3 12-2* Process Data
12-20 Control Instance
Range:
Function:
[None, 20, 21, 100,
101, 103]
Read only. Displays the originator-to-
target connection point. If no CIP
connection is present “None” is
displayed.
12-21 Process Data Config Write
Range:
Function:
[[0 - 9] PCD read 0 - 9] Configuration of readable process
data.
NOTE
For configuration of 2-word (32-bit) parameter read/write,
use 2 consecutive arrays in
12-21 Process Data Config Write
and
12-22 Process Data Config Read
.
12-22 Process Data Config Read
Range:
Function:
[[0 - 9] PCD read 0 - 9] Configuration of readable process
data.
12-28 Store Data Values
Option:
Function:
This parameter activates a function that stores
all parameter values in the non-volatile
memory (EEPROM) thus retaining parameter
values at power-down.
The parameter returns to “Off”.
[0]
*
Off
The store function is inactive.
[1]
Store All
set-ups
All parameter value will be stored in the non-
volatile memory, in all four setups.
12-29 Store Always
Option: Function:
Activates function that will always store received
parameter data in non-volatile memory (EEPROM).
[0]
*
Off
[1]
On
Parameters
MCA 121 EtherNet/IP
32
MG.90.J3.02 - VLT
®
is a registered Danfoss trademark
6
6