5.2 Danfoss FC Control Profile
5.2.1 Danfoss FC Control Profile
→
Illustration 5.1 (
= FC profile)
Bit
Bit value = 0
Bit value = 1
00
Reference value
External selection LSB
01
Reference value
External selection MSB
02
DC brake
Ramp
03
Coasting
No coasting
04
Quick stop
Ramp
05
Hold output frequency
Use ramp
06
Ramp stop
Start
07
No function
Reset
08
No function
Jog
09
Ramp 1
Ramp 2
10
Data invalid
Data valid
11
No function
Relay 01 active
12
No function
Relay 04 active
13
Parameter set-up
Selection LSB
14
Parameter set-up
Selection MSB
15
No function
Reverse
Explanation of Control Bits
Bits 00/01
Bits 00 and 01 are used to choose between the four
reference values, which are pre-programmed in
3-10 Preset
Reference
according to the following table:
Programmed
ref. value
Parameter
Bit 01
Bit 00
1
3-10 [0]
0
0
2
3-10 [1]
0
1
3
3-10 [2]
1
0
4
3-10 [3]
1
1
NOTE
In
8-56 Preset Reference Select
select a selection is made to
define how Bit 00/01 gates with the corresponding
function on the digital inputs.
Bit 02, DC brake:
Bit 02 = ‘0’ leads to DC braking and stop. Braking current
and duration are set in
2-01 DC Brake Current
and
2-02 DC
Braking Time
. Bit 02 = ‘1’ leads to ramping,
3-41 Ramp 1
Ramp up Time
Bit 03, Coasting:
Bit 03 = ‘0’ causes the frequency converter to immediately
"let go" of the motor (the output transistors are "shut off"),
so that it coasts to a standstill.
Bit 03 = ‘1’ enables the frequency converter to start the
motor if the other starting conditions have been fulfilled.
NOTE
In
8-50 Coasting Select
a selection is made to define how
Bit 03 gates with the corresponding function on a digital
input.
Bit 04, Quick stop:
Bit 04 = ‘0’ causes a stop, in which the motor speed is
ramped down to stop via
3-81 Quick Stop Ramp Time
.
Bit 05, Hold output frequency:
Bit 05 = ‘0’ causes the present output frequency (in Hz) to
freeze. The frozen output frequency can then be changed
only by means of the digital inputs (
5-10 Terminal 18
Digital Input
to
5-15 Terminal 33 Digital Input
) programmed
to
Speed up
and
Speed down
.
NOTE
If Freeze output is active, the frequency converter can only
be stopped by the following:
•
Bit 03 Coasting stop
•
Bit 02 DC braking
•
Digital input (
5-10 Terminal 18 Digital Input
to
5-15 Terminal 33 Digital Input
) programmed to
DC
braking
,
Coasting stop
or
Reset and coasting stop
How to Control
MCA 121 EtherNet/IP
MG.90.J3.02 - VLT
®
is a registered Danfoss trademark