5.3 ODVA Control Profile
5.3.1 Control Word under Instances 20/70
and 21/71
Set
to ODVA.
The control word in Instances 20 and 21 is defined as
follows:
→
NOTE
Bits 00 and 02 in Instance 20 are identical with bits 00 and
02 in the more extensive Instance 21.
Bit
Instance 20
Instance 21
Bit = 0
Bit =1
Bit = 0
Bit =1
00
Stop
Run
Fwd Stop
Run Fwd
01
-
-
Stop
Run Rev
02
No function Fault reset No function Fault reset
03
-
-
-
-
04
-
-
-
-
05
-
-
-
Net Ctrl
06
-
-
-
Net Ref
07-15
-
-
-
-
Explanation of the Bits:
Bit 0, Run Fwd:
Bit 0 = "0" means that the frequency converter has a stop
command. Bit 0 = "1" leads to a start command and the
frequency converter will start to run the motor clockwise.
Bit 1, Run Rev:
Bit 1 = "0" leads to a stop of the motor. Bit 1 = "1" leads to
a start of the motor.
Bit 2, Fault Reset:
Bit 2 = "0" means that there is no trip reset. Bit 2 = "1"
means that a trip is reset.
Bit 3, No function:
Bit 3 has no function.
Bit 4, No function:
Bit 4 has no function.
Bit 5, Net Control:
Bit 5 = "0" means that the frequency converter is
controlled from the standard inputs. Bit 5 = "1" means that
EIP controls the frequency converter.
NOTE
Please note that changes will affect parameters 8-50 to
8-56.
Bit 6, Net Reference:
Bit 6 = "0" Reference is from the standard inputs. Bit 6 =
"1" Reference is from EIP.
NOTE
Please note that changes will affect
3-15 Reference Resource
1
to
3-17 Reference Resource 3
. For the Speed reference, see
section
Bus speed reference value under Instances 20/70 and
21/71
.
5.3.2 Status Word under Instances 20/70
and 21/71
The status word in Instances 70 and 71 is defined as
follows:
→
NOTE
Bits 00 and 02 in Instance 70 are identical with bits 00 and
02 in the more extensive Instance 71.
Bit
Instance 70
Instance 71
Bit = 0
Bit =1
Bit = 0
Bit =1
00
No Fault
Fault
No Fault
Fault
01
-
-
-
Warning
02
-
Running 1
Fwd
-
Running 1 Fwd
03
-
-
-
Running 2 Rev.
04
-
-
-
Ready
05
-
-
-
Ctrl from Net
06
-
-
-
Ref. from Net
07
-
-
-
At ref.
08-15 -
-
State Attribute
How to Control
MCA 121 EtherNet/IP
24
MG.90.J3.02 - VLT
®