Mains
Supply
3
x
380
-
480
V
AC
-
Normal
overload
110%
for
1
minute
Frequency
converter
Typical
Shaft
Output
[kW]
P1K1
1.1
P1K5
1.5
P2K2
2.2
P3K0
3
P4K0
4
P5K5
5.5
P7K5
7.5
Typical
Shaft
Output
[HP]
at
460
V
1.5
2.0
2.9
4.0
5.0
7.5
10
IP
20
/
Chassis
(A2+A3
may
be
converted
to
IP21
using
a
conversion
kit.
(Please
see
also
items
Mechanical
mounting
and
IP
21/Type
1
Enclosure
kit
in
the
Design
Guide.))
A2
A2
A2
A2
A2
A3
A3
IP
55
/
Type
12
A4/A5
A4/A5
A4/A5
A4/A5
A4/A5
A5
A5
IP
66
/
NEMA
4X
A4/A5
A4/A5
A4/A5
A4/A5
A4/A5
A5
A5
Output
current
130BA058.10
Continuous
(3
x
380-440
V)
[A]
3
4.1
5.6
7.2
10
13
16
Intermittent
(3
x
380-440
V)
[A]
3.3
4.5
6.2
7.9
11
14.3
17.6
Continuous
(3
x
441-480
V)
[A]
2.7
3.4
4.8
6.3
8.2
11
14.5
Intermittent
(3
x
441-480
V)
[A]
3.0
3.7
5.3
6.9
9.0
12.1
15.4
Continuous
kVA
(400
V
AC)
[kVA]
2.1
2.8
3.9
5.0
6.9
9.0
11.0
Continuous
kVA
(460
V
AC)
[kVA]
2.4
2.7
3.8
5.0
6.5
8.8
11.6
Max.
input
current
130BA057.10
Continuous
(3
x
380-440
V)
[A]
2.7
3.7
5.0
6.5
9.0
11.7
14.4
Intermittent
(3
x
380-440
V)
[A]
3.0
4.1
5.5
7.2
9.9
12.9
15.8
Continuous
(3
x
441-480
V)
[A]
2.7
3.1
4.3
5.7
7.4
9.9
13.0
Intermittent
(3
x
441-480
V)
[A]
3.0
3.4
4.7
6.3
8.1
10.9
14.3
Additional
specifications
Estimated
power
loss
at
rated
max.
load
[W]
4)
58
62
88
116
124
187
255
(mains,
motor,
brake)
[[mm
2
/AWG]
2)
4/10
Weight
enclosure
IP20
[kg]
4.8
4.9
4.9
4.9
4.9
6.6
6.6
Weight
enclosure
IP21
[kg]
Weight
enclosure
IP55
[kg]
(A4/A5)
9.7/13.5
9.7/13.5
9.7/13.5
9.7/13.5
9.7/13.5
14.2
14.2
Weight
enclosure
IP66
[kg]
(A4/A5)
9.7/13.5
9.7/13.5
9.7/13.5
9.7/13.5
9.7/13.5
14.2
14.2
Efficiency
3)
0.96
0.97
0.97
0.97
0.97
0.97
0.97
Table
10.3
Mains
Supply
3
x
380
-
480
V
AC
Specifications
VLT
®
HVAC Drive Operating Instructions
MG11AH02 - VLT
®
is a registered Danfoss trademark
67
10