2.4.3 Motor Connection
WARNING
INDUCED VOLTAGE!
Run output motor cables from multiple frequency
converters separately. Induced voltage from output motor
cables run together can charge equipment capacitors even
with the equipment turned off and locked out. Failure to
run output motor cables separately could result in death
or serious injury.
•
For maximum wire sizes see
•
Comply with local and national electrical codes
for cable sizes
•
Motor wiring knockouts or access panels are
provided at the base of IP21 and higher
(NEMA1/12) units
•
Do not install power factor correction capacitors
between the frequency converter and the motor
•
Do not wire a starting or pole-changing device
between the frequency converter and the motor
•
Connect the 3-phase motor wiring to terminals
96 (U), 97 (V), and 98 (W)
•
Ground the cable in accordance with grounding
instructions provided
•
Torque terminals in accordance with the
information provided in
•
Follow motor manufacturer wiring requirements
The three following illustrations represent mains input,
motor, and earth grounding for basic frequency converters.
Actual configurations vary with unit types and optional
equipment.
130BA266.10
+DC
BR-
B
M
A
I
N
S
L1 L2 L3
91 92 93
RELA
Y 1 RELA
Y 2
99
- LC -
U V
W
MO
TOR
Illustration 2.9 Motor, Mains and Earth Wiring for A-Frame Sizes
91
L1
92
L2
93
L3
96
U
97
V
98
W
88
DC-
89
DC+
81
R-
8
R+
130BA390.11
99
95
Illustration 2.10 Motor, Mains and Earth Wiring for B-Frame Sizes
and Above Using Shielded Cable
Installation
VLT
®
HVAC Drive Operating Instructions
MG11AH02 - VLT
®
is a registered Danfoss trademark
15
2
2