9.1.2 Mains Supply 3x525–690 V AC
N450
N500
N560
N630
Normal load
NO
NO
NO
NO
(Normal overload=110% current during 60 s)
Typical shaft output at 550 V [kW]
355
400
450
500
Typical shaft output at 575 V [hp]
450
500
600
650
Typical shaft output at 690 V [kW]
450
500
560
630
Enclosure size
E1h/E3h
E1h/E3h
E1h/E3h
E1h/E3h
Output current (3-phase)
Continuous (at 550 V) [A]
470
523
596
630
Intermittent (60 s overload) (at 550 V) [A]
517
575
656
693
Continuous (at 575/690 V) [A]
450
500
570
630
Intermittent (60 s overload) (at 575/690 V) [A]
495
550
627
693
Continuous kVA (at 550 V) [kVA]
448
498
568
600
Continuous kVA (at 575 V) [kVA]
448
498
568
627
Continuous kVA (at 690 V) [kVA]
538
598
681
753
Maximum input current
Continuous (at 550 V) [A]
453
504
574
607
Continuous (at 575 V) [A]
434
482
549
607
Continuous (at 690 V) [A]
434
482
549
607
Maximum number and size of cables per phase (E1h)
- Mains and motor without brake [mm
2
(AWG)]
1)
5x240 (5x500
mcm)
5x240 (5x500
mcm)
5x240 (5x500
mcm)
6x240 (6x500
mcm)
- Mains and motor with brake [mm
2
(AWG)]
1)
4x240 (4x500
mcm)
4x240 (4x500
mcm)
4x240 (4x500
mcm)
5x240 (5x500
mcm)
- Brake or regeneration [mm
2
(AWG)]
1)
2x185 (2x350
mcm)
2x185 (2x350
mcm)
2x185 (2x350
mcm)
2x185 (2x350
mcm)
Maximum number and size of cables per phase (E3h)
- Mains and motor [mm
2
(AWG)]
1)
6x240 (6x500
mcm)
6x240 (6x500
mcm)
6x240 (6x500
mcm)
6x240 (6x500
mcm)
- Brake [mm
2
(AWG)]
1)
2x185 (2x350
mcm)
2x185 (2x350
mcm)
2x185 (2x350
mcm)
2x185 (2x350
mcm)
- Load share or regeneration [mm
2
(AWG)]
1)
4x185 (4x350
mcm)
4x185 (4x350
mcm)
4x185 (4x350
mcm)
4x185 (4x350
mcm)
Maximum external mains fuses [A]
2)
800
800
800
800
Estimated power loss at 600 V [W]
3)4)
6062
6879
8076
9208
Estimated power loss at 690 V [W]
3)4)
5939
6715
7852
8921
Efficiency
4)
0.98
0.98
0.98
0.98
Output frequency [Hz]
0–590
0–590
0–590
0–590
Heat sink overtemperature trip [
°
C (
°
F)]
110 (230)
110 (230)
110 (230)
110 (230)
Control card overtemperature trip [
°
C (
°
F)]
80 (176)
80 (176)
80 (176)
80 (176)
Power card overtemperature trip [
°
C (
°
F)]
85 (185)
85 (185)
85 (185)
85 (185)
Fan power card overtemperature trip [
°
C (
°
F)]
85 (185)
85 (185)
85 (185)
85 (185)
Active in-rush card overtemperature trip [
°
C (
°
F)]
85 (185)
85 (185)
85 (185)
85 (185)
Table 9.3 Technical Specifications, Mains Supply 3x525–690 V AC
Specifications
VLT® HVAC Drive FC 102
76
Danfoss A/S © 01/2017 All rights reserved.
MG16O102
9