5.1.15 20-** Drive Closed Loop
Par. No. #
Parameter description
Default value
2-set-up
Change
during
operation
Conver-
sion index
Type
20-0* Feedback
20-00
Feedback 1 Source
[0] No function
All set-ups
TRUE
-
Uint8
20-01
Feedback 1 Conversion
[0] Linear
All set-ups
TRUE
-
Uint8
20-8* PI Basic Settings
20-81
PI Normal/ Inverse Control
[0] Normal
All set-ups
TRUE
-
Uint8
20-83
PI Start Speed [Hz]
0 Hz
All set-ups
TRUE
-1
Uint16
20-84
On Reference Bandwidth
5 %
All set-ups
TRUE
0
Uint8
20-9* PI Controller
20-91
PI Anti Windup
[1] On
All set-ups
TRUE
-
Uint8
20-93
PI Proportional Gain
0.50 N/A
All set-ups
TRUE
-2
Uint16
20-94
PI Integral Time
20 s
All set-ups
TRUE
-2
Uint32
20-97
PI Feed Forward Factor
0 %
All set-ups
TRUE
0
Uint16
5.1.16 22-** Appl. Functions
Par. No. #
Parameter description
Default value
2-set-up
Change
during
operation
Conver-
sion index
Type
22-4* Sleep Mode
22-40
Minimum Run Time
10 s
All set-ups
TRUE
0
Uint16
22-41
Minimum Sleep Time
10 s
All set-ups
TRUE
0
Uint16
22-43
Wake-Up Speed [Hz]
10 N/A
All set-ups
TRUE
-1
Uint16
22-44
Wake-Up Ref./FB Diff
10 %
All set-ups
TRUE
0
Uint8
22-45
Setpoint Boost
0 %
All set-ups
TRUE
0
Int8
22-46
Maximum Boost Time
60 s
All set-ups
TRUE
0
Uint16
22-47
Sleep Speed [Hz]
0 N/A
All set-ups
TRUE
-1
Uint16
22-6* Broken Belt Detection
22-60
Broken Belt Function
[0] Off
All set-ups
TRUE
-
Uint8
22-61
Broken Belt Torque
10 %
All set-ups
TRUE
0
Uint8
22-62
Broken Belt Delay
10 s
All set-ups
TRUE
0
Uint16
5.1.17 24-** Appl. Functions 2
Par. No. #
Parameter description
Default value
2-set-up
Change during
operation
Conver-
sion index
Type
24-0* Fire Mode
24-00
FM Function
[0] Disabled
1 set-up
TRUE
-
Uint8
24-05
FM Preset Reference
0 %
All set-ups
TRUE
0
Int16
24-09
FM Alarm Handling
[1] Trip, Crit.Alarms
1 set-up
FALSE
-
Uint8
24-1* Drive Bypass
24-10
Drive Bypass Function
[0] Disabled
1 set-up
TRUE
-
Uint8
24-11
Drive Bypass Delay Time
0 s
1 set-up
TRUE
0
Uint16
Parameter Lists
VLT
®
HVAC Basic Drive FC 101 Programming Guide
MG18B302 - Rev. 2013-09-02
97
5
5
Summary of Contents for VLT HVAC Basic Drive FC 101
Page 2: ......
Page 104: ...www danfoss com drives MG18B302 130R0221 MG18B302 Rev 2013 09 02...