Drive
P2K2
P3K0
P3K7
P5K5
P7K5
P11K
P15K
Continuous (3x551–600 V) [A]
2.7
3.4
4.3
6.3
7.7
12.6
15.4
Intermittent (3x551–600 V) [A]
3.0
3.7
4.7
6.9
8.5
13.9
16.9
1
Applies for dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and typical control card power consump-
tions are included. For power loss data according to EN 50598-2, refer to Danfoss
website.
2
Efficiency measured at nominal current. For energy efficiency class, see
. For part load losses, see Danfoss
website.
Table 27: 3x525–600 V AC, 18.5–90 kW (25–125 hp), Enclosure Sizes H6–H8
Drive
P18K
P22K
P30K
P37K
P45K
P55K
P75K
P90K
Typical shaft output [kW]
18.5
22.0
30.0
37
45.0
55.0
75.0
90.0
Typical shaft output [hp]
25.0
30.0
40.0
50.0
60.0
70.0
100.0
125.0
Protection rating IP20
H6
H6
H6
H7
H7
H7
H8
H8
Maximum cable size in termi-
nals (mains, motor) [mm
2
(AWG)]
35 (2)
35 (2)
35 (2)
50 (1)
50 (1)
50 (1)
95 (0)
120 (4/0)
Output current - 40°C (104°F) ambient temperature
Continuous (3x525–550 V) [A]
28.0
36.0
43.0
54.0
65.0
87.0
105.0
137.0
Intermittent (3x525–550 V) [A]
30.8
39.6
47.3
59.4
71.5
95.7
115.5
150.7
Continuous (3x551–600 V) [A]
27.0
34.0
41.0
52.0
62.0
83.0
100.0
131.0
Intermittent (3x551–600 V) [A]
29.7
37.4
45.1
57.2
68.2
91.3
110.0
144.1
Maximum input current
Continuous (3x525–550 V) [A]
27.0
33.1
45.1
54.7
66.5
81.3
109.0
130.9
Intermittent (3x525–550 V) [A]
29.7
36.4
49.6
60.1
73.1
89.4
119.9
143.9
Continuous (3x551–600 V) [A]
25.7
31.5
42.9
52.0
63.3
77.4
103.8
124.5
Intermittent (3x551–600 V) [A]
28.3
34.6
47.2
57.2
69.6
85.1
114.2
137.0
Maximum mains fuses
3.2.4.5 Recommendation of Fuses and Circuit Breakers
Estimated power loss [W], best
case/typical
(1)
385
458
542
597
727
1092
1380
1658
Weight enclosure protection
rating IP54 [kg (lb)]
24.5 (54)
24.5 (54)
24.5 (54)
36.0
(79.3)
36.0
(79.3)
36.0
(79.3)
51.0
(112.4)
51.0
(112.4)
Efficiency [%], best case/typical
(2)
98.4
98.4
98.5
98.5
98.7
98.5
98.5
98.5
Output current - 50°C (122°F) ambient temperature
Continuous (3x525–550 V) [A]
19.6
25.2
30.1
37.8
45.5
60.9
73.5
95.9
Intermittent (3x525–550 V) [A]
21.6
27.7
33.1
41.6
50.0
67.0
80.9
105.5
Continuous (3x551–600 V) [A]
18.9
23.8
28.7
36.4
43.3
58.1
70.0
91.7
Intermittent (3x551–600 V) [A]
20.8
26.2
31.6
40.0
47.7
63.9
77.0
100.9
Specifications
Operating Guide | VLT® HVAC Basic Drive FC 101
AQ275641848264en-000101 / 132R0078
72 | Danfoss A/S © 2019.11