Drive
PK37
PK75
P1K5
P2K2
P3K0
P4K0
P5K5
P7K5
P11K
P15K
Continuous (3x380–440 V) [A]
1.2
2.1
3.5
4.7
6.3
8.3
11.2
15.1
22.1
29.9
Intermittent (3x380–440 V) [A]
1.3
2.3
3.9
5.2
6.9
9.1
12.3
16.6
24.3
32.9
Continuous (3x441–480 V) [A]
1.0
1.8
2.9
3.9
5.3
6.8
9.4
12.6
18.4
24.7
Intermittent (3x441–480 V) [A]
1.1
2.0
3.2
4.3
5.8
7.5
10.3
13.9
20.2
27.2
Maximum mains fuses
See
3.2.4.5 Recommendation of Fuses and Circuit Breakers
Estimated power loss [W], best
case/typical
(1)
13/15
16/21
46/57
46/58
66/83
95/11
8
104/1
31
159/1
98
248/2
74
353/3
79
Weight enclosure protection
rating IP20 [kg (lb)]
2.0
(4.4)
2.0
(4.4)
2.1
(4.6)
3.3
(7.3)
3.3
(7.3)
3.4
(7.5)
4.3
(9.5)
4.5
(9.9)
7.9
(17.4)
7.9
(17.4)
Efficiency [%], best case/typical
(2)
97.8/9
7.3
98.0/9
7.6
97.7/9
7.2
98.3/9
7.9
98.2/9
7.8
98.0/9
7.6
98.4/9
8.0
98.2/9
7.8
98.1/9
7.9
98.0/9
7.8
Output current - 50°C (122°F) ambient temperature
Continuous (3x380–440 V) [A]
1.04
1.93
3.7
4.85
6.3
8.4
10.9
14.0
20.9
28.0
Intermittent (3x380–440 V) [A]
1.1
2.1
4.07
5.4
6.9
9.2
12.0
15.4
23.0
30.8
Continuous (3x441–480 V) [A]
1.0
1.8
3.4
4.4
5.5
7.5
10.0
12.6
19.1
24.0
Intermittent (3x441–480 V) [A]
1.1
2.0
3.7
4.8
6.1
8.3
11.0
13.9
21.0
26.4
1
Applies for dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and typical control card power consump-
tions are included. For power loss data according to EN 50598-2, refer to Danfoss
website.
2
Typical: under rated condition. Best case: the optimal condition is adopt, such as the higher input voltage and lower switching frequency.
Table 23: 3x380–480 V AC, 18.5–90 kW (25–125 hp), Enclosure Sizes H5–H8
Drive
P18K
P22K
P30K
P37K
P45K
P55K
P75K
P90K
Typical shaft output [kW]
18.5
22.0
30.0
37.0
45.0
55.0
75.0
90.0
Typical shaft output [hp]
25.0
30.0
40.0
50.0
60.0
70.0
100.0
125.0
Protection rating IP20
H5
H5
H6
H6
H6
H7
H7
H8
Maximum cable size in termi-
nals (mains, motor) [mm
2
(AWG)]
16 (6)
16 (6)
35 (2)
35 (2)
35 (2)
50 (1)
95 (0)
120
(250MC
M)
Output current-40°C (104°F) ambient temperature
Continuous (3x380–440 V)[A]
37.0
42.5
61.0
73.0
90.0
106.0
147.0
177.0
Intermittent (3x380–440 V) [A]
40.7
46.8
67.1
80.3
99.0
116.0
161.0
194.0
Continuous (3x441–480 V) [A]
34.0
40.0
52.0
65.0
80.0
105.0
130.0
160.0
Intermittent (3x441–480 V) [A]
37.4
44.0
57.2
71.5
88.0
115.0
143.0
176.0
Maximum input current
Continuous (3x380–440 V) [A]
35.2
41.5
57.0
70.0
84.0
103.0
140.0
166.0
Intermittent (3x380–440 V) [A]
38.7
45.7
62.7
77.0
92.4
113.0
154.0
182.0
Continuous (3x441–480 V) [A]
29.3
34.6
49.2
60.6
72.5
88.6
120.9
142.7
Specifications
Operating Guide | VLT® HVAC Basic Drive FC 101
AQ275641848264en-000101 / 132R0078
68 | Danfoss A/S © 2019.11
Summary of Contents for VLT HVAC Basic Drive FC 101
Page 1: ...Operating Guide VLT HVAC Basic Drive FC 101...
Page 2: ......