3.2.4.5 Recommendation of Fuses and Circuit Breakers
NOTICE
In the event of malfunction, failure to follow the protection recommendation may result in damage to the drive.
Table 12: Fuses and Circuit Breakers
Circuit breaker
Fuse
UL
Non-UL
UL
Non-UL
Bussmann
Bussmann
Bussmann
Bussmann
Maxi‐
mum
fuse
Power [kW
(hp)]
Type RK5
Type RK1
Type J
Type T
Type G
3x200–240 V
IP20
0.25 (0.33)
–
–
FRS-R-10
KTN-R10
JKS-10
JJN-10
10
0.37 (0.5)
FRS-R-10
KTN-R10
JKS-10
JJN-10
10
0.75 (1)
FRS-R-10
KTN-R10
JKS-10
JJN-10
10
1.5 (2)
FRS-R-10
KTN-R10
JKS-10
JJN-10
10
2.2 (3)
FRS-R-15
KTN-R15
JKS-15
JJN-15
16
3.7 (5)
FRS-R-25
KTN-R25
JKS-25
JJN-25
25
5.5 (7.5)
FRS-R-50
KTN-R50
JKS-50
JJN-50
50
7.5 (10)
FRS-R-50
KTN-R50
JKS-50
JJN-50
50
11 (15)
FRS-R-80
KTN-R80
JKS-80
JJN-80
65
15 (20)
Cutler-Hammer
EGE3100FFG
Moeller NZMB1-
A125
FRS-R-100
KTN-R100
JKS-100
JJN-100
125
18.5 (25)
FRS-R-100
KTN-R100
JKS-100
JJN-100
125
22 (30)
Cutler-Hammer
JGE3150FFG
Moeller NZMB1-
A160
FRS-R-150
KTN-R150
JKS-150
JJN-150
160
30 (40)
FRS-R-150
KTN-R150
JKS-150
JJN-150
160
37 (50)
Cutler-Hammer
JGE3200FFG
Moeller NZMB1-
A200
FRS-R-200
KTN-R200
JKS-200
JJN-200
200
45 (60)
FRS-R-200
KTN-R200
JKS-200
JJN-200
200
3x380–480 V
IP20
Installation
Operating Guide | VLT® HVAC Basic Drive FC 101
AQ275641848264en-000101 / 132R0078
32 | Danfoss A/S © 2019.11