Drive
PK75
P1K5
P2K2
P3K0
P4KO
P5K5
P7K5
P11K
P15K
P18K
Weight enclosure protection
rating IP54 [kg (lb)]
5.3
(11.7)
5.3
(11.7)
5.3
(11.7)
5.3
(11.7)
5.3
(11.7)
7.2
(15.9)
7.2
(15.9)
13.8
(30.4)
13.8
(30.4)
13.8
(30.4)
Efficiency [%], best case/typical
(2)
98.0/9
7.6
97.7/9
7.2
98.3/9
7.9
98.2/9
7.8
98.0/9
7.6
98.4/9
8.0
98.2/9
7.8
98.1/9
7.9
98.0/9
7.8
98.1/9
7.9
Output current - 50°C (122°F) ambient temperature
Continuous (3x380–440 V) [A]
1.93
3.7
4.85
6.3
7.5
10.9
14.0
20.9
28.0
33.0
Intermittent (3x380–440 V) [A]
2.1
4.07
5.4
6.9
9.2
12.0
15.4
23.0
30.8
36.3
Continuous (3x441–480 V) [A]
1.8
3.4
4.4
5.5
6.8
10.0
12.6
19.1
24.0
30.0
Intermittent (3x441–480 V) [A]
2.0
3.7
4.8
6.1
8.3
11.0
13.9
21.0
26.4
33.0
1
Applies for dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and typical control card power consump-
tions are included. For power loss data according to EN 50598-2, refer to Danfoss
website.
2
Efficiency measured at nominal current. For energy efficiency class, see
. For part load losses, see Danfoss
website.
Table 25: 3x380–480 V AC, 22–90 kW (30–125 hp), Enclosure Sizes I6–I8
Drive
P22K
P30K
P37K
P45K
P55K
P75K
P90K
Typical shaft output [kW]
22.0
30.0
37.0
45.0
55.0
75.0
90.0
Typical shaft output [hp]
30.0
40.0
50.0
60.0
70.0
100.0
125.0
Protection rating IP54
I6
I6
I6
I7
I7
I8
I8
Maximum cable size in terminals
(mains, motor) [mm
2
(AWG)]
35 (2)
35 (2)
35 (2)
50 (1)
50 (1)
95 (3/0)
120 (4/0)
Output current - 40°C (104°F) ambient temperature
Continuous (3x380–440 V) [A]
44.0
61.0
73.0
90.0
106.0
147.0
177.0
Intermittent (3x380–440 V) [A]
48.4
67.1
80.3
99.0
116.6
161.7
194.7
Continuous (3x441–480 V) [A]
40.0
52.0
65.0
80.0
105.0
130.0
160.0
Intermittent (3x441–480 V) [A]
44.0
57.2
71.5
88.0
115.5
143.0
176.0
Maximum input current
Continuous (3x380–440 V) [A]
41.8
57.0
70.3
84.2
102.9
140.3
165.6
Intermittent (3x380–440 V) [A]
46.0
62.7
77.4
92.6
113.1
154.3
182.2
Continuous (3x441–480 V) [A]
36.0
49.2
60.6
72.5
88.6
120.9
142.7
Intermittent (3x441–480 V) [A]
39.6
54.1
66.7
79.8
97.5
132.9
157.0
Maximum mains fuses
See
3.2.4.5 Recommendation of Fuses and Circuit Breakers
Estimated power loss [W], best
case/typical
(1)
496
734
995
840
1099
1520
1781
Weight enclosure protection rat-
ing IP54 [kg (lb)]
27 (59.5)
27 (59.5)
27 (59.5)
45 (99.2)
45 (99.2)
65 (143.3)
65 (143.3)
Efficiency [%], best case/typical
(2)
98.0
97.8
97.6
98.3
98.2
98.1
98.3
Output current - 50°C (122°F) ambient temperature
Specifications
Operating Guide | VLT® HVAC Basic Drive FC 101
AQ275641848264en-000101 / 132R0078
70 | Danfoss A/S © 2019.11