6.1 Mains Supply
6.1.1 3x200–240 V AC
Table 20: 3x200–240 V AC, 0.25–7.5 kW (0.33–10 hp)
Drive
PK25
PK37
PK75
P1K5
P2K2
P3K7
P5K5
P7K5
Typical shaft output [kW]
0.25
0.37
0.75
1.5
2.2
3.7
5.5
7.5
Typical shaft output [hp]
0.33
0.5
1.0
2.0
3.0
5.0
7.5
10.0
Protection rating IP20
H1
H1
H1
H1
H2
H3
H4
H4
Maximum cable size in termi-
nals (mains, motor) [m
2
(AWG)]
4 (10)
4 (10)
4 (10)
4 (10)
4 (10)
4 (10)
16 (6)
16 (6)
Output current - 40°C (104°F) ambient temperature
Continuous (3x200–240 V) [A]
1.5
2.2
4.2
6.8
9.6
15.2
22.0
28.0
Intermittent (3x200–240 V) [A]
1.7
2.4
4.6
7.5
10.6
16.7
24.2
30.8
Maximum input current
Continuous 3x200–240 V) [A]
1.1
1.6
2.8
5.6
8.6/7.2
14.1/12.0
21.0/18.0
28.3/24.0
Intermittent (3x200–240V) [A]
1.2
1.8
3.1
6.2
9.5/7.9
15.5/13.2
23.1/19.8
31.1/26.4
Maximum mains fuses
3.2.4.5 Recommendation of Fuses and Circuit Breakers
Estimated power loss [W], Best
case/typical
(1)
12/14
15/18
21/26
48/60
80/102
97/120
182/204
229/268
Weight enclosure protection
rating IP20 [kg (lb)]
2.0 (4.4)
2.0 (4.4)
2.0 (4.4)
2.1 (4.6)
3.4 (7.5)
4.5 (9.9)
7.9 (17.4)
7.9 (17.4)
Efficiency [%], best case/typical
(2)
97.0/96.5
97.3/96.8
98.0/97.6
97.6/97.0
97.1/96.3
97.9/97.4
97.3/97.0
98.5/97.1
Output current - 50°C (122°F) ambient temperature
Continuous (3x200–240 V) [A]
1.5
1.9
3.5
6.8
9.6
13.0
19.8
23.0
Intermittent (3x200–240 V) [A]
1.7
2.1
3.9
7.5
10.6
14.3
21.8
25.3
1
Applies for dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and typical control card power consump-
tions are included. For power loss data according to EN 50598-2, refer to Danfoss
website.
2
Efficiency measured at nominal current. For energy efficiency class, see
. For part load losses, see Danfoss
website.
Table 21: 3x200–240 V AC, 11–45 kW (15–60 hp)
Drive
P11K
P15K
P18K
P22K
P30K
P37K
P45K
Typical shaft output [kW]
11.0
15.0
18.5
22.0
30.0
37.0
45.0
Typical shaft output [hp]
15.0
20.0
25.0
30.0
40.0
50.0
60.0
Protection rating IP20
H5
H6
H6
H7
H7
H8
H8
Specifications
Operating Guide | VLT® HVAC Basic Drive FC 101
AQ275641848264en-000101 / 132R0078
66 | Danfoss A/S © 2019.11