VLT
®
FCM Series
Externals:
- Enclosure .................................................................................................................................. IP 55 (IP56, IP66)
Please see special conditions for frequency range for IP 66 motors at the end of this section.
- Vibration test ................................................................................................................. (IEC 68 see page 93) 1 g
- Max. relative humidity .............................................................. 95 % (IEC 68-2-3) for storage/transport/operation
- Ambient temperature ............................................................................ Max. 40°C (24-hour average max. 35°C)
see Derating for high ambient temperature
- Min. ambient temperature in full operation ..................................................................................................... 0°C
- Min. ambient temperature at reduced performance ...................................................................................
-10°C
- Temperature during storage/transport .......................................................................................... -25 - +65/70°C
- Max. altitude above sea level .................................................................................................................... 1000 m
see Derating for air pressure
- EMC standards applied, Emission ................... EN 61000-6-3/EN 6100-6-4, EN 61800-3, EN 55011, EN 55014
- EMC standards applied, Immunity ................................................................................................................... EN
61000-6-2, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6, ENV 50204
- Safety standards applied, ..................................................................... EN 60146, EN 50178, EN 60204, UL508
NB!:
Please note that the normal IP 66 solution
is only intended for speed up to maximum
3000 rpm. If higher speed is needed, please
give notification when ordering.
Protection:
•
Thermal overload protection of motor
and electronics.
•
Monitoring of the intermediate circuit voltage
ensures that the inverter cuts out if the intermediate
circuit voltage gets too high or too low.
•
If a mains phase is missing, the inverter will cut
out when a load is placed on the motor.
Terminal arrangement (for installation see quick setup, MG.03.AX.62)
MG.03.H3.02 - VLT is a registered Danfoss trademark