N O T I C E
The type code is used in the fuse table. Write down the type code (T/C) and serial number (S/N) for future reference.
1
2
3
4
5
6
Enclosure: IP66 , Tamb. 40 C / 104 F
VLT
MADE IN
DENMARK
R
P/N: 134G2844 S/N: 010400G253
4.0kW(400V) / 5.0HP(460V)
IN: 3x380-480V 50/60Hz , 8.3/6.8A
OUT: 3x0-Vin 0-400Hz , 9.0/8.2A
o
*1 3 1 U 3 9 3 0 0 1 0 1 0 2 G 2 9 0 *
Drive Motor
www.danfoss.com
T/C: FCP106P4K0T4C66H1FSXXAXX
Enclosure rating: See manual
E134261 Ind. Contr. Eq.
o
7
8
9
10
11
e95na484.12
Illustration 1: Example of the Type Code on the Nameplate
1
Type code
2
Certifications
3
Protection rating
4
Bar code for manufacturer use
5
Certifications
6
Serial number
7
Enclosure type and IP protection rating, maximum
ambient temperature without derating
8
Output voltage, frequency, and current (at low/high
voltages)
9
Input voltage, frequency, and current (at low/high
voltages)
10
Power rating
11
Code number
1.8 Further Items Required
1 adapter plate
1 gasket, used between motor adapter plate and drive
1 motor connector
4 screws for fastening drive to adapter plate
4 screws for fastening motor adapter plate to motor
Crimp terminals
AMP standard power timer contacts female
3 pieces for motor terminals U, V, and W
2 pieces for thermistor (optional)
1 piece for grounding terminal
2 guiding pins (optional)
1.9 EMC-compliant Installation
For more information, refer to the operating guide.
Use shielded cables for motor and control wiring.
Connect the shield to the enclosures at both ends. If the shield connection points have a voltage potential difference, connect a
low impedance equalizing wire parallel to the shielded cable. Otherwise, break the shield connection on 1 end to prevent
ground current loops.
Avoid installation with twisted shield ends (pigtails), since this type of installation ruins the shield effect at high frequencies. Use
the cable clamps provided instead.
Ensure the same potential between drive and ground potential of the PLC.
Use star washers and galvanically conductive installation plates.
AN40855215838601-000101 /
130R1249
8 | Danfoss A/S © 2022.09
Instructions
VLT® DriveMotor FCP 106
Installation Guide
American English
Summary of Contents for VLT DriveMotor FCP 106
Page 2: ......
Page 48: ...VLT DriveMotor FCP 106 AN40855215838601 000101 130R1249 48 Danfoss A S 2022 09 ...
Page 49: ...VLT DriveMotor FCP 106 AN40855215838601 000101 130R1249 49 Danfoss A S 2022 09 ...
Page 50: ......
Page 51: ......