1.10 Motor-mount Installation of Drive
Procedure
Prepare a customized gasket to fit between the motor adapter plate and the motor.
Requirements for gasket:
Ensure that the gasket fulfils the ingress protection requirement.
Maintain the ground connection between the drive and the motor. The drive is grounded to the motor adapter plate.
Use a wire connection between motor and drive and ensure metallic contact between the motor adapter plate and
the motor.
Use a UL recognized material for the gasket, then UL listing or recognition is required for the assembled product.
Drill holes in the adapter plate so that it fits on the motor. See step 1 in the
Illustrations
section.
Crimp the wires for PE, motor terminals U, V, W, and motor thermistor M
T1
and M
T2
, see step 2.1. in the
Illustrations
section.
Fit the gasket between the motor and the motor bracket, see step 2.2 in the
Illustrations
section.
Place the adapter plate with the motor bracket on top of the motor, see step 2.3 in the
Illustrations
section.
Tighten the 4 screws on the motor bracket, see step 2.4 in the
Illustrations
section.
Fit the motor connector gasket on the motor bracket, see step 2.5 in the
Illustrations
section.
Attach the crimped wires to the motor connector, see step 2.6 in the
Illustrations
section.
Connect the motor connector the VLT® DriveMotor, see step 2.7 in the
Illustrations
section.
Tighten the VLT® DriveMotor to the motor.
1.11 Wiring to Mains and Control Terminals
Check the wiring diagram and cable entries in step 3 and 4 in the
Illustrations
section.
Procedure
Loosen the front cover screws, see step 5.1 in the
Illustrations
section.
Remove the front cover, see step 5.1 in the
Illustrations
section.
Mount cable glands fulfilling the requirements for the needed enclosure integrity.
Connect the ground wires to the ground terminals via the cable glands, see step 5.2 in the
Illustrations
section.
Connect the mains cable to terminals L1, L2, and L3 and tighten the screws, see step 5.2 in the
Illustrations
section.
Attach control and relay terminals, see step 6 in the
Illustrations
section.
Reassemble the cover and tighten the screws.
1.12 Power Losses and Efficiency
For power loss data including part load losses, see
https://ecosmart.mydrive.danfoss.com
1.13 Fuses and Cable Sizes
N O T I C E
WIRING GUIDELINES
All wiring must comply with local and national regulations regarding cross-section and ambient temperature requirements.
Loose connections can cause equipment faults or reduced performance. Tighten the terminals according to the proper torque
value shown in the illustrations. For power connections, use copper wire with a minimum 70 °C (158 °F) rating. For aluminum
wires, see the design guide.
For fuse ratings, see step 7 in the
Illustrations
section.
For power cable specifications rated for 45 ºC (113 ºF) ambient temperature at 400 V, see step 8 in the
Illustrations
section.
AN40855215838601-000101 /
130R1249
| 9
Danfoss A/S © 2022.09
Handbuch
VLT® DriveMotor FCP 106
Installationsanleitung
Deutsch
Summary of Contents for VLT DriveMotor FCP 106
Page 2: ......
Page 48: ...VLT DriveMotor FCP 106 AN40855215838601 000101 130R1249 48 Danfoss A S 2022 09 ...
Page 49: ...VLT DriveMotor FCP 106 AN40855215838601 000101 130R1249 49 Danfoss A S 2022 09 ...
Page 50: ......
Page 51: ......