5.3.10 Class ID 2Bh Acknowledge Handler Object
To manage message reception acknowledgements, necessary for change-of-state support, use class ID 2Bh acknowledge
handler object. The attributes supported for this class are listed in
.
Attribute
Access
Name
Data
type
Minimum/
Maximum
Default
Description
1
Set
ACK timer
UINT
0–65535
16
Time to wait for ACK before resending.
2
Get/Set
Retry timer
USINT
0–255
1
Number of ACK-timeouts to wait before
producing.
RetryLimit_Reache event.
3
Get/Set
COS
UINT
–
–
Connection instance ID
Table 5.15 Class ID 0x2B
5.4 Danfoss Object Classes
Use the Danfoss classes for read and write of all parameter
values of the frequency converters. A corresponding object
class is defined for each parameter group.
shows
the classes supported, and their relationship to the
parameters.
The class instance and attribute act in the following way:
•
100 added to the parameter group = the value
for the class.
•
100 added to the remaining parameter number =
the value for the instance.
•
100 added to the array index of the parameter =
the value for the attribute.
Parameter range
Class
Parameter 0-00 – 0-99
Class 100
Parameter 1-00 – 1-99
Class 101
Parameter 2-00 – 2-99
Class 102
Parameter 3-00 – 3-99
Class 103
Parameter 4-00 – 4-99
Class 104
Parameter 5-00 – 5-99
Class 105
Parameter 6-00 – 6-99
Class 106
Parameter 7-00 – 7-99
Class 107
Parameter 8-00 – 8-99
Class 108
Parameter 10-00 – 10-99
Class 110
Parameter 11-00 – 11-99
Class 111
Parameter 13-00 – 13-99
Class 113
Parameter 14-00 – 14-99
Class 114
Parameter 15-00 – 15-99
Class 115
Parameter 16-00 – 16-99
Class 116
Table 5.16 Danfoss Classes
5.4.1 Examples
Examples: (fictitious parameters) (all values in decimal)
•
Parameter 0-01 Language
[index 0] = Class 100;
instance 101; attribute 100
•
Parameter 1-00 Configuration Mode
[index 0] =
Class 101; instance 100; attribute 100
•
Parameter 3-41 Ramp 1 Ramp Up Time
[index 0] =
Class 103; instance 141; attribute 100
•
Parameter 1-55 U/f Characteristic - U
[index 3] =
Class 101; instance 155; attribute 103
•
Parameter 6-54 Terminal 42 Output Timeout Preset
[index 9] = Class 106; instance 154; attribute 109
•
Parameter 10-01 Baud Rate Select
[index 0] = Class
110; instance 101; attribute 100
Parameter Access
Programming Guide
MG92F102
Danfoss A/S © 12/2015 All rights reserved.