1.3.4 Dimensions
NOTICE!
The figure in
Table 1.6
is with LCP but all dimensions are the same without LCP.
A
a
b
B
C
0
D
130BB614.10
e
f
a
e
130BC246.10
Enclosure
Height (in [mm])
Width (in [mm])
Depth (in
[mm])
Mounting hole (in [mm])
Max.
Weight
Frame
IP Class
A
A
1)
a
B
b
C
d
e
f
lb [kg]
H3
IP20
10 [255]
13 [329]
9.5 [240] 3.9 [100]
2.9 [74]
8.1 [206]
0.4
[11]
0.2 [5.5]
0.3
[8.1]
9.9 [4.5]
H4
IP20
11.7 [296]
14.1 [359] 10.8 [275] 5.3 [135] 4.1 [105]
9.5 [241]
0.5
[12.6]
0.3 [7]
0.33
[8.4]
17.4 [7.9]
H5
IP20
13.2 [334]
15.8 [402] 12.4 [314] 5.9 [150] 4.7 [120]
10 [255]
0.5
[12.6]
0.3 [7]
0.34
[8.5]
21 [9.5]
Table 1.6 Dimensions
1) Including decoupling plate
The dimensions are only for the physical units, but when installing in an application it is necessary to add space for free air
passage both above and below the units. The amount of space for free air passage is listed in
Table 1.5
.
1.3.5 Electrical Installation in General
All cabling must comply with national and local regulations on cable cross-sections and ambient temperature. Copper
conductors required, (167
°
F [75
°
C]) recommended.
Enclosure
Torque [Nm]
Frame
IP class
Line
Compressor
connection
DC connection
Control
terminals
Ground
Relay
H3
IP20
1.4
0.8
0.8
0.5
0.8
0.5
H4
IP20
1.2
1.2
1.2
0.5
0.8
0.5
H5
IP20
1.2
1.2
1.2
0.5
0.8
0.5
Table 1.7 Enclosure H3-H5