D. Operation keys and LEDs
13 [Hand On]: Starts the compressor and enables control of
the adjustable frequency drive via the LCP.
NOTICE!
Terminal 27 Digital Input (
5-12 Terminal 27 Digital
Input
) has stop inverse as default setting. This
means that [Hand On] does not start the
compressor if there is no 24 V to terminal 27.
Connect terminal 12 to terminal 27.
14 [Off/Reset]: Stops the compressor (Off). If in alarm mode,
the alarm is reset.
15 [Auto On]: The adjustable frequency drive is controlled
either via control terminals or serial communication.
Table 1.12 Legend to
Figure 1.12
1.4.2 The Start-up Wizard
The built-in wizard menu guides the installer through the
set-up of the adjustable frequency drive in a clear and
structured manner to set up an open-loop application. An
open-loop application is here an application with a start
signal, analog reference (voltage or current) and optionally
also relay signals (but no feedback signal from the process
applied).
FC
+24 V
DIG IN
DIG IN
DIG IN
DIG IN
COM DIG IN
A OUT/D OUT
A OUT/D OUT
18
19
27
29
42
55
50
53
54
20
12
01
02
03
04
05
06
R2
R1
+
0-10 V
Start
+10 V
A IN
A IN
COM
130BD872.10
45
Reference
15
PRESSURE SWITCH
Figure 1.13 Open-loop Application
The wizard is initially be shown after power-up until any
parameter has been changed. The wizard can always be
accessed again through the Quick Menu. Press [OK] to start
the wizard. Press [Back] to return to the status screen.
130BB629.10
Press OK to start Wizard
Push Back to skip it
Set-up 1
Figure 1.14 Start-up/Quit Wizard