Closed-loop wizard
Parameter
Option
Default
Function
0-01 Language
[0] English
[1] Deutsch
[2] Francais
[3] Dansk
[4] Spanish
[5] Italiano
[28] Bras.port
0
Select the language for the display.
0-06 GridType
[0] 200–240 V/50 Hz/IT grid
[1] 200–240 V/50 Hz/Delta
[2] 200–240 V/50 Hz
[10] 380–440 V/50 Hz/IT grid
[11] 380–440 V/50 Hz/Delta
[12] 380–440 V/50 Hz
[20] 440–480 V/50 Hz/IT grid
[21] 440–480 V/50 Hz/Delta
[22] 440–480 V/50 Hz
[30] 525–600 V/50 Hz/IT grid
[31] 525–600 V/50 Hz/Delta
[32] 525–600 V/50 Hz
[100] 200–240 V/60 Hz/IT grid
[101] 200–240 V/60 Hz/Delta
[102] 200–240 V/60 Hz
[110] 380–440 V/60 Hz/IT grid
[111] 380–440 V/60 Hz/Delta
[112] 380–440 V/60 Hz
[120] 440–480 V/60 Hz/IT grid
[121] 440–480 V/60 Hz/Delta
[122] 440–480 V/60 Hz
[130] 525–600 V/60 Hz/IT grid
[131] 525–600 V/60 Hz/Delta
[132] 525–600 V/60 Hz
Size related
Select the operating mode for restart upon
reconnection of the adjustable frequency
drive to AC line voltage after power-down.
0-60 Main Menu Password
0–999
0
Define the password for access to the LCP.
1-00 Configuration Mode
[0] Open-loop
[3] Closed-loop
[0] Open-loop
Select closed-loop.
1-13 Compressor Selection
[24] VZH028-R410A
[25] VZH035-R410A
[26] VZH044-R410A
Size related
Select the used compressor.
3-02 Minimum Reference
-4999.0–200 Hz
0 Hz
The minimum reference is the lowest value
obtainable by summing all references.
3-03 Maximum Reference
0–200 Hz
200 Hz
The maximum reference is the highest
obtainable by summing all references
3-10 Preset Reference
-100–100%
0%
Set up a fix setpoint n preset reference [0].
3-15 Reference 1 Source
[0] No function
[1] Analog in 53
[2] Analog in 54
[7] Pulse input 29
[11] Local bus reference
[1] Analog in 53
Select the input to be used for the reference
signal.
3-41 Ramp 1 Ramp Up Time
0.05–3600.0 s
30.00 s
Ramp-up time from 0 to
1-25 Motor Nominal
Speed
.
3-42 Ramp 1 Ramp Down Time
0.05–3600.0 s
30.00 s
Ramp-down time from rated motor speed to
0.