Common drives and motor problems

Procedure to conduct the 

dynamic test to check the 

IGBT 

Faults in the drive

Drive temperature sensor / 

Over temperature fault

Current sensor fault

Dynamic tests have to be done without the 
compressor connected to UVW connector, and 
the Drive has to be programmed to a proxy 50Hz 
at start.

The Dynamic test can indicate if one of the IGBT 
doesn’t switch, and the output voltage will drop 
on the fault terminal, UVW.

Program the multimeter to AC 1000V RM.

•  Connect the positive terminal of the multimeter 

lead to the U connector, and connect the 
negative terminal to the V terminal.

•  Connect the positive terminal of the multimeter 

lead to the U connector, and connect the 
negative terminal to the W terminal.

•  Connect the positive terminal of the multimeter 

lead to the V connector, and connect the 
negative terminal to the W terminal.

The meter reading will be between 360V - 380V 
when performing the dynamic test at 400V 
mains and 50Hz/3000RPM output depending on 
instrument used.

The reading should be within ±1.5 percent. When 
the reading exceeds this, the IGBT is damaged. 

•  If the drive is stopped and cooled, the LCP 

reading shall show the ambient temperature.

•  If not, the temperature sensor or temperature 

measurement circuit is defective.

When a current sensor fails, it is indicated 
sometimes by an earth fault alarm that cannot be 
reset, even with the motor leads disconnected.

•  Disconnect the motor from the drive, and then 

observe the current in the display of the drive.

•  If the motor is disconnected from the unit, the 

LCP shall read out 0.00A.

•  If anything else is shown, this indicates a 

defective current sensor.

Figure 11: Dynamic test

Note: Both faults above are non-reparable. Drive needs to be replaced

The motor or motor wiring can develop a phase 
to phase or phase to ground short resulting in 
alarm indication and a trip of the unit.

A motor with the unbalanced or non-
symmetrical impedances on all the three phases 
can result in uneven or rough operation or 
unbalanced output current.

•  To determine whether the problem is internal 

or external to the drive, disconnect the motor 
from the drive output terminals. 

•  Perform the dynamic output test procedure on 

all three phases with a digital voltmeter. 

•  

If the three voltage measurements are 
balanced, the drive is functioning correctly. 
The problem is therefore external to the drive.

• 

 If the voltage measurements are not 
balanced, the drive is malfunctioning. 

This typically means that one or more output 
IGBT is not switching on and off correctly.

If one of the IGBT fails, the drive is damaged 
and must be replaced.

IGBT, Motor or load 

problems 

12

FRCC.PC.036.A2.02

Check List

Summary of Contents for VLT CDS 302

Page 1: ...Compressor Drives Troubleshooting Check List CDS 302 CDS 303 http cc danfoss com...

Page 2: ......

Page 3: ...n 7 Environmental conditions 7 Proper clearance 7 Trouble shooting 8 Fault Symptoms Display of the drive 8 No display blank display 8 Intermittent display 8 Fault Symptoms in the compressor motor 9 Co...

Page 4: ...sary use of resources and limit the number of NFF The purpose of this check list is to facilitate users field technicians engineers and service personnel working with Danfoss frequency converters to i...

Page 5: ...an remain charged even when the frequency converter is not powered To avoid electrical hazards disconnect AC mains any permanent magnet type motors and any remote DC link power supplies including batt...

Page 6: ...start Figure 2 WARNINGS and ALARM messages are displayed when the frequency converter fault detects a faulty condition WARNINGS and ALARM Alarm Log Check the content of the alarm log 5 latest alarms a...

Page 7: ...e subject The drive should be mounted solidly or the use of shock mounts employed Under specific conditions these units can be operated within a maximum ambient temperature of 50 C 24h average maximum...

Page 8: ...pletely dark An error code exists in the drive which indicates that communications may have failed with the control card This is typically seen when an option card has been installed in the drive and...

Page 9: ...t verify that the unit is properly powered up and there is no warning or alarm The most common cause of this is either incorrect control logic or an incorrectly programmed drive Such occurrences will...

Page 10: ...zero or missing Check the control wiring to ensure that a proper reference signal is present at the drive input terminals and that the unit is properly programmed to accept the signal provided Improp...

Page 11: ...otor settings references and limits and I O configuration The drives must be set up correctly for the compressors connected to it If not the compressor may fail to start or use higher than normal amou...

Page 12: ...ature measurement circuit is defective When a current sensor fails it is indicated sometimes by an earth fault alarm that cannot be reset even with the motor leads disconnected Disconnect the motor fr...

Page 13: ...ned drive trips Detrimental Effects To These Systems May Include The Following Pressure flow temperature signal transmitter signal distortion or aberrant behaviour Radio and TV interference Telephone...

Page 14: ...negative terminal of the multimeter meter lead to the positive DC bus Connect the positive terminal of the multimeter lead to the input terminal L1 L2 L3 in turn The multimeter should show the diode...

Page 15: ...Step 1 Step 2 Step 3 Connect the positive terminal of the multimeter lead to the positive DC bus Connect the negative terminal of the multimeter lead to the motor terminal U V W in turn The multimete...

Page 16: ...rminal of the meter lead to the negative DC bus Connect the negative terminal of the meter lead to the motor terminals U V W in turn The multimeter should show diode drop around 0 4 volts Figure 19 Th...

Page 17: ......

Page 18: ...ooftops chillers residential air conditioners heatpumps coldrooms supermarkets milk tank cooling and industrial cooling processes http cc danfoss com Danfoss Inverter Scrolls Danfoss Turbocor Compress...

Reviews: