380–500 V
Enclosure
Power [kW]
Recommended
fuse size
Recommended
maximum fuse
Recommended circuit
breaker Moeller
Maximum trip level
[A]
A1
0.37–1.5
gG-10
gG-25
PKZM0-16
16
A2
0.37–4.0
gG-10 (0.37-3)
gG-16 (4)
gG-25
PKZM0-25
25
A3
5.5–7.5
gG-16
gG-32
PKZM0-25
25
A4
0.37-4
gG-10 (0.37-3)
gG-16 (4)
gG-32
PKZM0-25
25
A5
0.37–7.5
gG-10 (0.37-3)
gG-16 (4–7.5)
gG-32
PKZM0-25
25
B1
11–15
gG-40
gG-80
PKZM4-63
63
B2
18.5–22
gG-50 (18.5)
gG-63 (22)
gG-100
NZMB1-A100
100
B3
11–15
gG-40
gG-63
PKZM4-50
50
B4
18.5–30
gG-50 (18.5)
gG-63 (22)
gG-80 (30)
gG-125
NZMB1-A100
100
C1
30–45
gG-80 (30)
gG-100 (37)
gG-160 (45)
gG-160
NZMB2-A200
160
C2
55–75
aR-200 (55)
aR-250 (75)
aR-250
NZMB2-A250
250
C3
37–45
gG-100 (37)
gG-160 (45)
gG-150 (37)
gG-160 (45)
NZMB2-A200
150
C4
55–75
aR-200 (55)
aR-250 (75)
aR-250
NZMB2-A250
250
Table 8.14 380–500 V, Enclosure Types A, B, and C
Specifications
VLT
®
AutomationDrive FC 301/302
66
Danfoss A/S © 07/2015 All rights reserved.
MG33AQ02
8
8
Summary of Contents for VLT AutomationDrive FC 301