Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
130BB934.10
Function
Setting
Parameter 5-10 Ter
minal 18 Digital
Input
[8] Start
Parameter 5-11 Ter
minal 19 Digital
Input
[10]
Reversing
Parameter 5-12 Ter
minal 27 Digital
Input
[0] No
operation
Parameter 5-14 Ter
minal 32 Digital
Input
[16] Preset
ref bit 0
Parameter 5-15 Ter
minal 33 Digital
Input
[17] Preset
ref bit 1
Parameter 3-10 Pre
set Reference
Preset reference 0
Preset reference 1
Preset reference 2
Preset reference 3
25%
50%
75%
100%
* = Default value
Notes/comments:
D IN 37 is an option.
Table 6.9 Start/Stop with Reversing and 4 Preset Speeds
6.1.4 External Alarm Reset
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
130BB928.10
Function
Setting
Parameter 5-11 T
erminal 19
Digital Input
[1] Reset
* = Default value
Notes/comments:
D IN 37 is an option.
Table 6.10 External Alarm Reset
6.1.5 RS485
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
R1
R2
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
01
02
03
04
05
06
-
61
68
69
RS-485
+
130BB685.10
Function
Setting
Parameter 8-30 P
rotocol
FC*
Parameter 8-31 A
ddress
1*
Parameter 8-32 B
aud Rate
9600*
* = Default value
Notes/comments:
Select protocol, address, and
baud rate in the above-
mentioned parameters.
D IN 37 is an option.
Table 6.11 RS485 Network Connection
Application Set-up Examples
VLT
®
AutomationDrive FC 301/302
34
Danfoss A/S © 07/2015 All rights reserved.