Parameters
130BB927.10
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
A53
U - I
4 - 20mA
+
-
Function
Setting
Parameter 6-12 T
erminal 53 Low
Current
4 mA*
Parameter 6-13 T
erminal 53 High
Current
20 mA*
Parameter 6-14 T
erminal 53 Low
Ref./Feedb. Value
0 Hz
Parameter 6-15 T
erminal 53 High
Ref./Feedb. Value
50 Hz
* = Default value
Notes/comments:
D IN 37 is an option.
Table 6.4 Analog Speed Reference (Current)
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
A53
U - I
≈ 5kΩ
130BB683.10
Function
Setting
Parameter 6-10 T
erminal 53 Low
Voltage
0.07 V*
Parameter 6-11 T
erminal 53 High
Voltage
10 V*
Parameter 6-14 T
erminal 53 Low
Ref./Feedb. Value
0 Hz
Parameter 6-15 T
erminal 53 High
Ref./Feedb. Value
1500 Hz
* = Default value
Notes/comments:
D IN 37 is an option.
Table 6.5 Speed Reference (Using a Manual Potentiometer)
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
130BB804.10
Function
Setting
Parameter 5-10 T
erminal 18
Digital Input
[8] Start
*
Parameter 5-12 T
erminal 27
Digital Input
[19] Freeze
Reference
Parameter 5-13 T
erminal 29
Digital Input
[21] Speed Up
Parameter 5-14 T
erminal 32
Digital Input
[22] Speed
Down
* = Default value
Notes/comments:
D IN 37 is an option.
Table 6.6 Speed Up/Down
Start (18)
Freeze ref (27)
Speed up (29 )
Speed down (32 )
Speed
Reference
130BB840.11
Illustration 6.1 Speed Up/Down
Application Set-up Examples
VLT
®
AutomationDrive FC 301/302
32
Danfoss A/S © 07/2015 All rights reserved.
MG33AQ02
6
6