6.1.6 Motor Thermistor
WARNING
THERMISTOR INSULATION
Risk of personal injury or equipment damage.
•
Use only thermistors with reinforced or double
insulation to meet PELV insulation
requirements.
Parameters
130BB686.12
VLT
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
50
53
54
55
42
39
A53
U - I
D IN
37
Function
Setting
Parameter 1-90
Motor Thermal
Protection
[2] Thermistor
trip
Parameter 1-93 T
hermistor Source
[1] Analog
input 53
* = Default Value
Notes/comments:
If only a warning is required,
set
parameter 1-90 Motor
Thermal Protection
to
[1]
Thermistor warning
.
D IN 37 is an option.
Table 6.12 Motor Thermistor
6.1.7 SLC
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
R1
R2
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
01
02
03
04
05
06
130BB839.10
Function
Setting
Parameter 4-30 M
otor Feedback Loss
Function
[1] Warning
Parameter 4-31 M
otor Feedback
Speed Error
100 RPM
Parameter 4-32 M
otor Feedback Loss
Timeout
5 s
Parameter 7-00 Sp
eed PID Feedback
Source
[2] MCB 102
Parameter 17-11 R
esolution (PPR)
1024*
Parameter 13-00 S
L Controller Mode
[1] On
Parameter 13-01 S
tart Event
[19] Warning
Parameter 13-02 S
top Event
[44] Reset key
Parameter 13-10 C
omparator
Operand
[21] Warning
no.
Parameter 13-11 C
omparator
Operator
[1] ≈
*
Parameter 13-12 C
omparator Value
90
Parameter 13-51 S
L Controller Event
[22]
Comparator
0
Parameter 13-52 S
L Controller Action
[32] Set
digital out A
low
Parameter 5-40 Fu
nction Relay
[80] SL
digital output
A
*=Default Value
Table 6.13 Using SLC to Set a Relay
Notes/comments:
Exceeding the limit in the feedback monitor issues
warning
90, Feedback monitor
. The SLC monitors
warning 90,
Feedback monitor
, and if the warning becomes true, relay 1
is triggered.
External equipment indicates if service is required. If the
feedback error goes below the limit again within 5 s, the
frequency converter continues, and the warning
disappears. But relay 1 is still triggered until [Reset] is
pressed on the LCP.
Application Set-up Examples
Operating Instructions
MG33AQ02
Danfoss A/S © 07/2015 All rights reserved.
35
6
6