background image

demand normally stays below the maximum capacity of
the lead pump

4.2.7 Staging/De-staging in Mixed Pump

Configurations 

Two methods are used to decide when pumps should be
staged or de-staged.

Speed of the frequency converters

Feedback pressure exceeding the normal
operating range

In a mixed pump configuration with more than one
frequency converter both methods are used.
In the following example, feedback is referred to as
pressure. 

Staging

When the master drive receives a start command a
variable speed pump is selected, and started using one of
the available frequency converters.

If the system pressure drops, the speed of the frequency
converter increases to meet the demand for more flow.
While maintaining the pressure, if the frequency converter
exceeds 

27-31 Stage On Speed [RPM]

 (or 

27-32 Stage On

Speed [Hz]

) and remains above that speed for 

27-33 Stage

Off Speed [RPM]

 (or 

27-34 Stage Off Speed [Hz]

) time, the

next variable speed pump is staged on.

If the Cascade Controller is unable to maintain the system
pressure with all variable speed pumps running at
maximum, it will stage on fixed speed pumps. A fixed
speed pump will be staged on when the pressure goes
below the setpoint by 

27-20 Normal Operating Range

percentage and stays there for the Staging Delay time
(

27-23 Staging Delay

).

De-staging

If the system pressure increases, the speed of the
frequency converter decreases to maintain pressure. If the
frequency converter drops below 

27-33 Stage Off Speed

[RPM]

 (or 

27-32 Stage On Speed [Hz]

) and stays there for the

time chosen in 

27-24 Destaging Delay

, a variable speed

pump will be staged off.

If the system pressure is too high with only one frequency
converter running at minimum speed, it will de-stage fixed
speed pumps. A fixed speed pump will be de-staged when
the pressure goes above the setpoint in 

27-20 Normal

Operating Range

 and stays there for the time chosen in

27-24 Destaging Delay

. If the system demand continues to

drop the system will enter sleep mode.

4.2.8 Override Staging/De-staging

Normal staging and de-staging handles most of the
situations in typical applications but the Cascade Controller
in stage and de-stage pumps immediately in response to
large changes in system demand.

Staging

When the system pressure drops below the override limit
(

27-21 Override Limit

), the Cascade Controller will

immediately stage on a pump to meet the demand for
more flow. 

If the system pressure continues to stay below 

27-21 Override Limit

 for 

27-25 Override Hold Time

, the

Cascade Controller will then stage on the next pump. This
repeats until all pumps are on or until the system pressure
drops below the Override Limit.

De-staging

When the system pressure exceeds 

27-21 Override Limit

,

the Cascade Controller immediately de-stages a pump to
reduce the pressure.

If the system pressure continues to stay above 

27-21 Override Limit

 for 

27-25 Override Hold Time

, the

Cascade Controller de-stages another pump. This will
repeat until only the lead pump is left on or until the
pressure stabilizes.

27-21 Override Limit

 is set as a % of the Maximum

Reference. It defines a point above and below the system
Setpoint where Override staging and de-staging will occur.

4.2.9 Minimum Speed De-staging

To reduce emergency usage the Cascade Controller will
de-stage a pump if the lead pump is running at minimum
speed for 

27-27 Min Speed Destage Delay

4.2.10 Fixed Speed only Operation 

Fixed speed only operation keeps critical systems
operating even if all variable speed pumps are unavailable
to the Cascade Controller. In this situation, the Cascade
Controller maintains system pressure by turning on and off
fixed speed pumps. 

Staging

If all the variable speed pumps are unavailable and the
system pressure goes below 

27-22 Fixed Speed Only

Operating Range

 for the Staging Delay time (

27-23 Staging

Delay

), a fixed speed pump will be turned on.

Configuring the System

VLT

®

 AQUA Drive MCO 101/MCO 102

20

MI38C402 - VLT

®

 is a registered Danfoss trademark

4

4

Summary of Contents for vlt aqua

Page 1: ...MAKING MODERN LIVING POSSIBLE V VLTp AQUA Drive Cascade Controller Options MCO 101 102 Operating Instructions...

Page 2: ...arge before performing any service or repair work The amount of wait time is listed in the Discharge Time table Failure to wait the specified time after power has been removed before doing service or...

Page 3: ...Safety VLT AQUA Drive MCO 101 MCO 102 MI38C402 VLT is a registered Danfoss trademark...

Page 4: ...1 Before Start 12 3 1 2 Extended Cascade Controller MCO 101 12 3 1 3 Advanced Cascade Controller MCO 102 14 4 Configuring the System 16 4 1 Configuring the Extended and Advanced Cascade Controller 16...

Page 5: ...ttings 27 2 26 5 1 6 Staging Speed 27 3 28 5 1 7 Staging Settings 27 4 29 5 1 8 Alternation Settings 27 5 30 5 1 9 Digital Inputs 27 6 31 5 1 10 Connections 27 7 35 5 1 11 Readouts 27 9 36 5 2 Paramet...

Page 6: ...For further information see 2 Application Types The Extended Cascade Controller can be used in two different modes with the extended features controlled by parameter group 27 to extend the number of a...

Page 7: ...Instructions provide details on installation and operation of the frequency converter The VLT AutomationDrive FC 302 Programming Guide provides greater detail on working with parameters and many appl...

Page 8: ...connected pumps and frequency converters to the master The necessary hardware is explained in the following hardware configuration examples 2 2 1 Extension of Basic Cascade Parameter Group 25 Control...

Page 9: ...able speed pump In this configuration the VLT AQUA Drive controls one variable speed pump and up to 8 fixed speed pumps The fixed speed pumps are staged and de staged as needed through contactors dire...

Page 10: ...ges the pumps on and off according to system requirements Compared to traditional cascade control the number of running pumps is controlled by speed instead of feedback To obtain the highest energy sa...

Page 11: ...f the benefits of the master follower configuration with some of the initial cost savings of the fixed speed configuration It is a good choice when the extra capacity of the fixed pumps is rarely need...

Page 12: ...0 100 100 100 200 200 C 1 100 200 300 400 2 3 4 130BD073 10 Illustration 2 7 Valid Configuration Example NOTICE Invalid configurations like in Illustration 2 8 will still run but will not stage on all...

Page 13: ...70 0 RELAY 1 8 Pump 1 to Drive 1 27 70 1 RELAY 2 16 Pump 2 to Drive 1 27 70 9 RELAY 10 74 Pump 3 to Mains 27 70 10 RELAY 11 75 Pump 4 to Mains 27 70 11 RELAY 12 76 Pump 5 to Mains 2 2 4 Using Soft Sta...

Page 14: ...last drive running after de staging This is achieved by giving the connected pump the highest priority in the parameters for runtime balancing e g by programming the drive with the MCO 101 or the MCO...

Page 15: ...590 Hz the difference from standard software is that it cannot be flashed i e neither downgraded nor upgraded 3 1 2 Extended Cascade Controller MCO 101 The MCO 101 option includes 3 pieces of change o...

Page 16: ...ow voltage parts and PELV systems see Illustration 3 4 1 1 1 1 10 2 3 4 5 6 7 8 9 12 11 2 2 3 1 1 1 1 10 2 3 4 5 6 7 8 9 12 11 3 3 3 1 1 1 1 10 2 3 4 5 6 7 8 9 12 11 2 2 2 130BA176 11 Illustration 3 4...

Page 17: ...g kit depending on the enclosure Type Description Ordering number Options MCF 105 Mounting Kit frame size A2 and A3 40 mm for one C Option 130B7530 MCF 105 Mounting Kit Frame size A5 130B7532 MCF 105...

Page 18: ...d relief the cables by the enclosed cable strips 6 Fit the extended cradle and terminal cover 7 Remount the LCP 8 Connect power to the frequency converter Wiring the Terminals 130BB025 11 Illustration...

Page 19: ...should equally balance the running hours between the pumps then use the default values 27 17 Motor Starters All fixed speed pumps must be the same 27 18 Spin time for unused pumps Depends on the size...

Page 20: ...ed the system pressure is still maintained but the pumps are beginning to operate below their peak efficiency points De staging a pump will cause the speed of the frequency converters to increase into...

Page 21: ...arameter group 27 0 Control Status to check on the status of the Cascade Controller and to control individual pumps Select a specific pump to view the current status the current running hours and the...

Page 22: ...Pumps If a pump is only needed occasionally the Cascade Controller balances the running hours of the pumps through alternation If a pump is not used in 72 hours a pump spin is triggered The spin time...

Page 23: ...in 27 24 Destaging Delay If the system demand continues to drop the system will enter sleep mode 4 2 8 Override Staging De staging Normal staging and de staging handles most of the situations in typi...

Page 24: ...tion of the theoretical curve results in step wise adjusted set points following this curve Set point 1 is the minimum pressure required when the system is running with only one pump operating and und...

Page 25: ...on Select the reference input to be used for the first reference signal 3 15 Reference 1 Source Option Function 3 15 Reference 1 Source 3 16 Reference 2 Source and 3 17 Reference 3 Source define up to...

Page 26: ...Digital Output Option Function 0 No operation 1 Control ready 2 Drive ready 3 Drive rdy rem ctrl 4 Stand by no warning 5 Running 6 Running no warning 8 Run on ref no warn 9 Alarm 5 30 Terminal 27 Digi...

Page 27: ...gital Input applicable value 5 52 Term 29 Low Ref Feedb Value Range Function This parameter is available for FC 302 only 5 53 Term 29 High Ref Feedb Value Range Function 100 999999 999 999999 999 Ente...

Page 28: ...tatus is a readout parameter showing the status of each pump in the system Option Function 6 Offline Fault The pump is not available for use by the Cascade Controller and the pump is connected to main...

Page 29: ...speed pumps All fixed speed pumps must be configured the same Possible choices are 0 Direct Online 1 Soft Starter Adds a delay when staging and de staging corresponding to the soft starter ramp time s...

Page 30: ...cations the override limit is used as wake up condition See 6 1 Master Follower for further information Setpoint SBW 27 70 OBW 27 71 SBW 27 70 OBW 27 71 Actual head OBW timer 27 25 130BA370 11 Illustr...

Page 31: ...he lead pump must be running at minimum speed while the system feedback is still inside the normal operating band before a pump will be turned off to save energy Energy savings may be 27 27 Min Speed...

Page 32: ...Delay and more than one variable speed pump is on a variable speed pump will be turned off 5 1 7 Staging Settings 27 4 Parameters for configuring staging transitions 27 40 Auto Tune Staging Settings...

Page 33: ...tically calculated values If 27 43 Staging Threshold and 27 44 Destaging 27 44 Destaging Threshold Range Function Threshold are modified from the bus or LCP then the new values will be used but will c...

Page 34: ...e when the pump is running below a speed where interruption in operation will not affect the process This minimizes the system disturbance caused by alternations The value is entered as a of the capac...

Page 35: ...85 Latched Pump Derag 120 Lead Pump Start 27 61 Terminal X66 3 Digital Input Option Function 121 Lead Pump Alternation 130 Pump 1 Interlock 131 Pump 2 Interlock 132 Pump 3 Interlock 133 Pump 4 Interl...

Page 36: ...21 Lead Pump Alternation 130 Pump 1 Interlock 27 63 Terminal X66 7 Digital Input Option Function 131 Pump 2 Interlock 132 Pump 3 Interlock 133 Pump 4 Interlock 134 Pump 5 Interlock 135 Pump 6 Interloc...

Page 37: ...ock 131 Pump 2 Interlock 132 Pump 3 Interlock 27 65 Terminal X66 11 Digital Input Option Function 133 Pump 4 Interlock 134 Pump 5 Interlock 135 Pump 6 Interlock 136 Pump 7 Interlock 137 Pump 8 Interlo...

Page 38: ...Pump 3 to Drive 2 27 70 Relay 27 70 Relay is an array parameter used to setup the function of the option relays Depending on which option is installed only the available relays will be visible If Exte...

Page 39: ...ence is a readout parameter that shows the reference output for use with follower drives This reference is available even when the master drive is stopped This is the speed that the frequency converte...

Page 40: ...t ups TRUE 0 Uint1 6 25 26 Destage At No Flow 0 Disabled All set ups TRUE Uint8 Par No Parameter description Default value 4 set up Chan ge duri ng oper ation Con ver sion ind ex Type 25 27 Stage Func...

Page 41: ...Alternation 0 N A All set ups TRUE 0 Uint8 Table 5 1 5 2 2 27 Cascade CTL Option Par No Parameter description Default value 4 set up Chan ge duri ng oper atio n Con ver sion ind ex Type 27 0 Control S...

Page 42: ...mp Up Delay 2 0 s All set ups TRUE 1 Uint1 6 Par No Parameter description Default value 4 set up Chan ge duri ng oper atio n Con ver sion ind ex Type 27 43 Staging Threshold Expres sionLimit All set u...

Page 43: ...erminal X66 13 Digital Input 0 No operation All set ups TRUE Uint8 27 7 Connections Par No Parameter description Default value 4 set up Chan ge duri ng oper atio n Con ver sion ind ex Type 27 70 Relay...

Page 44: ...e 1 1 Small 1601 Reference 0 21 Display Line 1 2 Small 1652 Feedback 0 22 Display Line 1 3 Small 1614 Motor current 0 23 Display Line 2 Large 1613 Frequency 0 24 Display Line 3 Large 2794 Cascade Syst...

Page 45: ...are 1 Set parameter 27 34 01 higher than the minimum speed in 4 11 Motor Speed Low Limit RPM 4 12 Motor Speed Low Limit Hz to enable sleep function setting it to zero will disable the function 2 Set 2...

Page 46: ...ime Hours 19 M Manual Pump Control 18 Master Drive 4 Master Follower Configuration 7 Min Speed De stage Delay 27 27 28 Mixed Pump Configuration 9 8 Pump Selection 16 Multiple Drives 19 N Number Of Fre...

Page 47: ...Supported Configurations 5 Symbols iii U Unequal Size Pump Configuration 8 V Variable Speed Pumps 4 Index VLT AQUA Drive MCO 101 MCO 102 44 MI38C402 VLT is a registered Danfoss trademark...

Page 48: ...Index VLT AQUA Drive MCO 101 MCO 102 MI38C402 VLT is a registered Danfoss trademark 45...

Page 49: ...www danfoss com drives MI38C402 130R0345 MI38C402 Rev 2012 08 21...

Reviews: