5.2 Parameter Lists
NOTICE
Be aware that parameter group
25-** Cascade Controller
is only to be used for the Basic Cascade Controller or if
one of the options is used for extending the number of
pumps of the Basic Cascade Controller.
In all other cases use parameter group
27-** Cascade CTL
Option
.
5.2.1 25-** Cascade Controller
Par.
No.
#
Parameter
description
Default
value
4-set-
up
Chan
ge
duri
ng
oper
ation
Con
ver-
sion
ind
ex
Type
25-0* System Settings
25-00
Cascade
Controller
Expres-
sionLimit
2 set-
ups
FALSE
-
Uint8
25-02 Motor Start
[0] Direct
on Line
2 set-
ups
FALSE
-
Uint8
25-04 Pump Cycling
Expres-
sionLimit
All
set-
ups
TRUE
-
Uint8
25-05 Fixed Lead Pump
Expres-
sionLimit
2 set-
ups
FALSE
-
Uint8
25-06
Number of
Pumps
2 N/A
2 set-
ups
FALSE
0
Uint8
25-2* Bandwidth Settings
25-20
Staging
Bandwidth
Expres-
sionLimit
All
set-
ups
TRUE
0
Uint8
25-21
Override
Bandwidth
100 %
All
set-
ups
TRUE
0
Uint8
25-22
Fixed Speed
Bandwidth
casco_sta
ging_ban
dwidth
(P2520)
All
set-
ups
TRUE
0
Uint8
25-23
SBW Staging
Delay
15 s
All
set-
ups
TRUE
0
Uint1
6
25-24
SBW Destaging
Delay
15 s
All
set-
ups
TRUE
0
Uint1
6
25-25 OBW Time
10 s
All
set-
ups
TRUE
0
Uint1
6
25-26
Destage At No-
Flow
[0]
Disabled
All
set-
ups
TRUE
-
Uint8
Par.
No.
#
Parameter
description
Default
value
4-set-
up
Chan
ge
duri
ng
oper
ation
Con
ver-
sion
ind
ex
Type
25-27 Stage Function
Expres-
sionLimit
All
set-
ups
TRUE
-
Uint8
25-28
Stage Function
Time
15 s
All
set-
ups
TRUE
0
Uint1
6
25-29 Destage Function
Expres-
sionLimit
All
set-
ups
TRUE
-
Uint8
25-30
Destage Function
Time
15 s
All
set-
ups
TRUE
0
Uint1
6
25-4* Staging Settings
25-40
Ramp Down
Delay
10 s
All
set-
ups
TRUE
-1
Uint1
6
25-41 Ramp Up Delay
2 s
All
set-
ups
TRUE
-1
Uint1
6
25-42
Staging
Threshold
Expres-
sionLimit
All
set-
ups
TRUE
0
Uint8
25-43
Destaging
Threshold
Expres-
sionLimit
All
set-
ups
TRUE
0
Uint8
25-44
Staging Speed
[RPM]
0 RPM
All
set-
ups
TRUE
67
Uint1
6
25-45
Staging Speed
[Hz]
0 Hz
All
set-
ups
TRUE
-1
Uint1
6
25-46
Destaging Speed
[RPM]
0 RPM
All
set-
ups
TRUE
67
Uint1
6
25-47
Destaging Speed
[Hz]
0 Hz
All
set-
ups
TRUE
-1
Uint1
6
25-5* Alternation Settings
25-50
Lead Pump
Alternation
Expres-
sionLimit
All
set-
ups
TRUE
-
Uint8
25-51 Alternation Event
[0]
External
All
set-
ups
TRUE
-
Uint8
25-52
Alternation Time
Interval
24 h
All
set-
ups
TRUE
74
Uint1
6
25-53
Alternation Timer
Value
0 N/A
All
set-
ups
TRUE
0
VisSt
r[7]
Parameter Descriptions
VLT
®
AQUA Drive MCO 101/MCO 102
MI38C402 - VLT
®
is a registered Danfoss trademark
37