background image

6-61

Terminal

 X30/8

 Min.

 Scale

6-62

Terminal

 X30/8

 Max.

 Scale

6-63

Terminal

 X30/8

 Output

 Bus

 Control

6-64

Terminal

 X30/8

 Output

 Timeout

 Preset

8-**

Comm.

 and

 Options

8-0*

General

 Settings

8-01

Control

 Site

8-02

Control

 Source

8-03

Control

 Timeout

 Time

8-04

Control

 Timeout

 Function

8-05

End-of-Timeout

 Function

8-06

Reset

 Control

 Timeout

8-07

Diagnosis

 Trigger

8-08

Readout

 Filtering

8-09

Communication

 Charset

8-1*

Control

 Settings

8-10

Control

 Profile

8-13

Configurable

 Status

 Word

 STW

8-3*

FC

 Port

 Settings

8-30

Protocol

8-31

Address

8-32

Baud

 Rate

8-33

Parity

 /

 Stop

 Bits

8-34

Estimated

 cycle

 time

8-35

Minimum

 Response

 Delay

8-36

Maximum

 Response

 Delay

8-37

Maximum

 Inter-Char

 Delay

8-4*

FC

 MC

 protocol

 set

8-40

Telegram

 Selection

8-42

PCD

 write

 configuration

8-43

PCD

 read

 configuration

8-5*

Digital/Bus

8-50

Coasting

 Select

8-52

DC

 Brake

 Select

8-53

Start

 Select

8-54

Reversing

 Select

8-55

Set-up

 Select

8-56

Preset

 Reference

 Select

8-7*

BACnet

8-70

BACnet

 Device

 Instance

8-72

MS/TP

 Max

 Masters

8-73

MS/TP

 Max

 Info

 Frames

8-74

“I-Am”

 Service

8-75

Initialisation

 Password

8-8*

FC

 Port

 Diagnostics

8-80

Bus

 Message

 Count

8-81

Bus

 Error

 Count

8-82

Slave

 Messages

 Rcvd

8-83

Slave

 Error

 Count

8-84

Slave

 Messages

 Sent

8-85

Slave

 Timeout

 Errors

8-89

Diagnostics

 Count

8-9*

Bus

 Jog

 /

 Feedback

8-90

Bus

 Jog

 1

 Speed

8-91

Bus

 Jog

 2

 Speed

8-94

Bus

 Feedback

 1

8-95

Bus

 Feedback

 2

8-96

Bus

 Feedback

 3

9-**

Profibus

9-00

Setpoint

9-07

Actual

 Value

9-15

PCD

 Write

 Configuration

9-16

PCD

 Read

 Configuration

9-18

Node

 Address

9-22

Telegram

 Selection

9-23

Parameters

 for

 Signals

9-27

Parameter

 Edit

9-28

Process

 Control

9-44

Fault

 Message

 Counter

9-45

Fault

 Code

9-47

Fault

 Number

9-52

Fault

 Situation

 Counter

9-53

Profibus

 Warning

 Word

9-63

Actual

 Baud

 Rate

9-64

Device

 Identification

9-65

Profile

 Number

9-67

Control

 Word

 1

9-68

Status

 Word

 1

9-71

Profibus

 Save

 Data

 Values

9-72

ProfibusDriveReset

9-75

DO

 Identification

9-80

Defined

 Parameters

 (1)

9-81

Defined

 Parameters

 (2)

9-82

Defined

 Parameters

 (3)

9-83

Defined

 Parameters

 (4)

9-84

Defined

 Parameters

 (5)

9-90

Changed

 Parameters

 (1)

9-91

Changed

 Parameters

 (2)

9-92

Changed

 Parameters

 (3)

9-93

Changed

 Parameters

 (4)

9-94

Changed

 Parameters

 (5)

9-99

Profibus

 Revision

 Counter

10-**

CAN

 Fieldbus

10-0*

Common

 Settings

10-00

CAN

 Protocol

10-01

Baud

 Rate

 Select

10-02

MAC

 ID

10-05

Readout

 Transmit

 Error

 Counter

10-06

Readout

 Receive

 Error

 Counter

10-07

Readout

 Bus

 Off

 Counter

10-1*

DeviceNet

10-10

Process

 Data

 Type

 Selection

10-11

Process

 Data

 Config

 Write

10-12

Process

 Data

 Config

 Read

10-13

Warning

 Parameter

10-14

Net

 Reference

10-15

Net

 Control

10-2*

COS

 Filters

10-20

COS

 Filter

 1

10-21

COS

 Filter

 2

10-22

COS

 Filter

 3

10-23

COS

 Filter

 4

10-3*

Parameter

 Access

10-30

Array

 Index

10-31

Store

 Data

 Values

10-32

Devicenet

 Revision

10-33

Store

 Always

10-34

DeviceNet

 Product

 Code

10-39

Devicenet

 F

 Parameters

11-**

LonWorks

11-0*

LonWorks

 ID

11-00

Neuron

 ID

11-1*

LON

 Functions

11-10

Drive

 Profile

11-15

LON

 Warning

 Word

11-17

XIF

 Revision

11-18

LonWorks

 Revision

11-2*

LON

 Param.

 Access

11-21

Store

 Data

 Values

12-**

Ethernet

12-0*

IP

 Settings

12-00

IP

 Address

 Assignment

12-01

IP

 Address

12-02

Subnet

 Mask

12-03

Default

 Gateway

12-04

DHCP

 Server

12-05

Lease

 Expires

12-06

Name

 Servers

12-07

Domain

 Name

12-08

Host

 Name

12-09

Physical

 Address

12-1*

Ethernet

 Link

 Parameters

12-10

Link

 Status

12-11

Link

 Duration

12-12

Auto

 Negotiation

12-13

Link

 Speed

12-14

Link

 Duplex

12-2*

Process

 Data

12-20

Control

 Instance

12-21

Process

 Data

 Config

 Write

12-22

Process

 Data

 Config

 Read

12-27

Primary

 Master

12-28

Store

 Data

 Values

12-29

Store

 Always

12-3*

EtherNet/IP

12-30

Warning

 Parameter

12-31

Net

 Reference

12-32

Net

 Control

12-33

CIP

 Revision

12-34

CIP

 Product

 Code

12-35

EDS

 Parameter

12-37

COS

 Inhibit

 Timer

12-38

COS

 Filter

12-4*

Modbus

 TCP

12-40

Status

 Parameter

12-41

Slave

 Message

 Count

12-42

Slave

 Exception

 Message

 Count

12-8*

Other

 Ethernet

 Services

12-80

FTP

 Server

12-81

HTTP

 Server

12-82

SMTP

 Service

12-89

Transparent

 Socket

 Channel

 Port

12-9*

Advanced

 Ethernet

 Services

12-90

Cable

 Diagnostic

12-91

Auto

 Cross

 Over

12-92

IGMP

 Snooping

12-93

Cable

 Error

 Length

12-94

Broadcast

 Storm

 Protection

12-95

Broadcast

 Storm

 Filter

12-96

Port

 Config

12-98

Interface

 Counters

12-99

Media

 Counters

13-**

Smart

 Logic

13-0*

SLC

 Settings

13-00

SL

 Controller

 Mode

13-01

Start

 Event

13-02

Stop

 Event

13-03

Reset

 SLC

13-1*

Comparators

13-10

Comparator

 Operand

13-11

Comparator

 Operator

13-12

Comparator

 Value

13-2*

Timers

13-20

SL

 Controller

 Timer

13-4*

Logic

 Rules

13-40

Logic

 Rule

 Boolean

 1

13-41

Logic

 Rule

 Operator

 1

13-42

Logic

 Rule

 Boolean

 2

13-43

Logic

 Rule

 Operator

 2

13-44

Logic

 Rule

 Boolean

 3

13-5*

States

13-51

SL

 Controller

 Event

13-52

SL

 Controller

 Action

14-**

Special

 Functions

14-0*

Inverter

 Switching

14-00

Switching

 Pattern

14-01

Switching

 Frequency

14-03

Overmodulation

14-04

PWM

 Random

14-1*

Mains

 On/Off

14-10

Mains

 Failure

14-11

Mains

 Voltage

 at

 Mains

 Fault

14-12

Function

 at

 Mains

 Imbalance

14-2*

Reset

 Functions

14-20

Reset

 Mode

14-21

Automatic

 Restart

 Time

14-22

Operation

 Mode

14-23

Typecode

 Setting

14-25

Trip

 Delay

 at

 Torque

 Limit

14-26

Trip

 Delay

 at

 Inverter

 Fault

14-28

Production

 Settings

14-29

Service

 Code

14-3*

Current

 Limit

 Ctrl.

14-30

Current

 Lim

 Ctrl,

 Proportional

 Gain

14-31

Current

 Lim

 Ctrl,

 Integration

 Time

14-32

Current

 Lim

 Ctrl,

 Filter

 Time

14-4*

Energy

 Optimising

14-40

VT

 Level

14-41

AEO

 Minimum

 Magnetisation

14-42

Minimum

 AEO

 Frequency

14-43

Motor

 Cosphi

14-5*

Environment

14-50

RFI

 Filter

14-51

DC

 Link

 Compensation

14-52

Fan

 Control

14-53

Fan

 Monitor

14-55

Output

 Filter

14-59

Actual

 Number

 of

 Inverter

 Units

14-6*

Auto

 Derate

14-60

Function

 at

 Over

 Temperature

14-61

Function

 at

 Inverter

 Overload

14-62

Inv.

 Overload

 Derate

 Current

15-**

Drive

 Information

15-0*

Operating

 Data

15-00

Operating

 Hours

15-01

Running

 Hours

15-02

kWh

 Counter

15-03

Power

 Up's

15-04

Over

 Temp's

15-05

Over

 Volt's

15-06

Reset

 kWh

 Counter

15-07

Reset

 Running

 Hours

 Counter

15-08

Number

 of

 Starts

15-1*

Data

 Log

 Settings

15-10

Logging

 Source

15-11

Logging

 Interval

15-12

Trigger

 Event

15-13

Logging

 Mode

15-14

Samples

 Before

 Trigger

15-2*

Historic

 Log

15-20

Historic

 Log:

 Event

15-21

Historic

 Log:

 Value

15-22

Historic

 Log:

 Time

15-23

Historic

 Log:

 Date

 and

 Time

15-3*

Alarm

 Log

15-30

Alarm

 Log:

 Error

 Code

15-31

Alarm

 Log:

 Value

15-32

Alarm

 Log:

 Time

15-33

Alarm

 Log:

 Date

 and

 Time

15-4*

Drive

 Identification

15-40

FC

 Type

15-41

Power

 Section

15-42

Voltage

15-43

Software

 Version

15-44

Ordered

 Typecode

 String

15-45

Actual

 Typecode

 String

15-46

Frequency

 Converter

 Ordering

 No

15-47

Power

 Card

 Ordering

 No

15-48

LCP

 Id

 No

15-49

SW

 ID

 Control

 Card

15-50

SW

 ID

 Power

 Card

15-51

Frequency

 Converter

 Serial

 Number

15-53

Power

 Card

 Serial

 Number

15-55

Vendor

 URL

15-56

Vendor

 Name

15-59

CSIV

 Filename

15-6*

Option

 Ident

15-60

Option

 Mounted

15-61

Option

 SW

 Version

15-62

Option

 Ordering

 No

15-63

Option

 Serial

 No

15-70

Option

 in

 Slot

 A

15-71

Slot

 A

 Option

 SW

 Version

15-72

Option

 in

 Slot

 B

15-73

Slot

 B

 Option

 SW

 Version

Programming

VLT

®

 AQUA Drive D-Frame

Operating Instructions

MG21A202 - VLT

®

 is a registered Danfoss trademark

45

5

5

Summary of Contents for VLT AQUA Drive D-Frame

Page 1: ...MAKING MODERN LIVING POSSIBLE Operating Instructions 110 400 kW D Frame VLT AQUA Drive FC 200...

Page 2: ...nnected to the AC mains the motor may be started by means of an external switch a serial bus command an input reference signal or a cleared fault condition Use appropriate cautions to guard against an...

Page 3: ...Safety VLT AQUA Drive D Frame Operating Instructions MG21A202 VLT is a registered Danfoss trademark...

Page 4: ...ent 3 5 mA 13 2 4 2 2 Earthing Grounding IP20 Enclosures 14 2 4 2 3 Earthing Grounding IP21 54 Enclosures 14 2 4 3 Motor Connection 14 2 4 3 1 Terminal Locations D1h D4h 15 2 4 3 2 Terminal Locations...

Page 5: ...and Copying Parameter Settings 38 4 2 1 Uploading Data to the LCP 39 4 2 2 Downloading Data from the LCP 39 4 3 Restoring Default Settings 39 4 3 1 Recommended Initialisation 39 4 3 2 Manual Initialis...

Page 6: ...nitions 59 8 5 Fault Messages 60 9 Basic Troubleshooting 67 9 1 Start Up and Operation 67 10 Specifications 70 10 1 Power dependent Specifications 70 10 2 General Technical Data 73 10 3 Fuse Tables 78...

Page 7: ...nector 13 Earth ground 6 Serial bus terminal switch 14 Motor output terminals 96 U 97 V 98 W 7 Analog switches A53 A54 15 Mains input terminals 91 L1 92 L2 93 L3 8 Relay 1 01 02 03 16 TB5 IP21 54 only...

Page 8: ...or circuit breaker must be opened to de energize the frequency converter and the cover of the options cabinet must be removed For frequency converters purchased with a disconnect contactor or circuit...

Page 9: ...r status issues warnings or alarms for fault conditions starts and stops the motor optimizes energy efficiency and offers many more control monitoring and efficiency functions Operation and monitoring...

Page 10: ...h D3h D4h D4h D4h D4h 690 V D3h D3h D3h D4h D4h D4h D4h Table 1 4 kW Rated Frequency Converters HP High Overload 100 125 150 200 250 300 350 350 HP Normal Overload 125 150 200 250 300 350 400 450 460...

Page 11: ...rent for peak motor performance Motor size and frequency converter power must match for proper overload protection If frequency converter rating is less than motor full motor output cannot be achieved...

Page 12: ...D2h D4h 204 m3 hr 120 CFM 840 m3 hr 500 CFM Table 2 2 Airflow 2 3 2 Lifting Always lift the frequency converter using the dedicated lifting eyes Use a bar to avoid bending the lifting holes CAUTION T...

Page 13: ...ment can be hazardous All electrical work must conform to national and local electrical codes It is strongly recommended that instal lation start up and maintenance be performed only by trained and qu...

Page 14: ...PNP 27 24V 0V D IN OUT 0V PNP 24V NPN D IN OUT 0V 24V 29 24V NPN 0V PNP 0V PNP 24V NPN 33 D IN 32 D IN 1 2 ON A53 U I S201 ON 2 1 A54 U I S202 ON 0 20mA OFF 0 10V 95 400Vac 2A P 5 00 R 82 R 81 37 D I...

Page 15: ...e current draw the quicker the trip response The overload provides Class 20 motor protection See 8 Warnings and Alarms for details on the trip function Because the motor wiring carries high frequency...

Page 16: ...er motor power and control wiring Use the clamps provided with the equipment for proper earth connections ground connections Do not earth ground one frequency converter to another in a daisy chain fas...

Page 17: ...bles from multiple frequency converters separately Induced voltage from output motor cables run together can charge equipment capacitors even with the equipment turned off and locked out Failure to ru...

Page 18: ...A MAINS TERMINALS MAINS TERMINAL SECTION B B MOTOR TERMINALS MOTOR TERMINAL 130BC305 10 Illustration 2 7 Terminal Locations D1h A A B B 83 3 3 0 0 0 188 7 4 244 9 6 0 0 0 290 11 4 272 10 7 0 0 0 22 0...

Page 19: ...168 4 7 GROUND 143 4 6 42 4 2 0 0 0 68 1 3 125 8 5 183 5 7 245 8 10 299 8 12 353 8 14 377 6 15 284 2 11 0 0 0 R S T U V W 4X M10x20 STUD WITH NUT SECTION B B MOTOR TERMINALS AND BRAKE TERMINALS MOTOR...

Page 20: ...MAINS TERMINAL SECTION B B MOTOR TERMINALS AND BRAKE TERMINALS TERMINAL BRAKE REGEN MOTOR TERMINAL 130BC333 10 Illustration 2 11 Terminal Locations D4h 1 190 7 5 75 3 0 126 4 9 95 3 7 2 130BC534 10 Il...

Page 21: ...Illustration 2 13 Terminal Locations D5h with Disconnect Option 33 1 3 0 0 62 2 4 101 4 140 5 5 163 6 4 185 7 3 191 7 5 224 8 8 256 10 1 263 10 4 293 11 5 GROUND 3X 511 20 1 0 0 517 20 4 623 24 5 727...

Page 22: ...N TERMINALS SECTION A A MAINS TERMINALS R S T U V W 130BC537 11 TB6 Terminal block for contactor Illustration 2 15 Terminal Locations D6h with Contactor Option A A 99 3 9 153 6 0 0 0 0 225 8 9 45 1 8...

Page 23: ...4 0 0 0 MAINS TERMINAL SECTION A A MAINS TERMINALS R S T 130BC541 10 Illustration 2 17 Terminal Locations D6h with Circuit Breaker Option Installation VLT AQUA Drive D Frame Operating Instructions 20...

Page 24: ...5 21 4 0 0 119 4 7 276 10 9 0 0 MAINS TERMINAL BRAKE TERMINAL MOTOR TERMINAL 4X M10X20 STUD WITH NUT SECTION B B MOTOR TERMINALS SECTION A A MAINS TERMINALS BRAKE REGEN TEMINALS R S T U V W Illustrati...

Page 25: ...75 14 8 290 11 4 0 0 257 10 1 309 12 1 0 0 MOTOR TERMINAL BRAKE TERMINAL MAINS TERMINAL 4X M10X20 STUD WITH NUT SECTION B B MOTOR TERMINALS BRAKE REGEN TERMINALS SECTION A A MAINS TERMINALS R S T U V...

Page 26: ...5 0 0 MAINS TERMINAL MOTOR TERMINAL BRAKE TERMINAL 4X M10X20 STUD WITH NUT SECTION A A MAINS TERMINALs BRAKE REGEN TERMINALS SECTION B B MOTOR TERMINALS R S T U V W 130BC544 11 TB6 Terminal block for...

Page 27: ...SECTION C C MAINS TERMINALS 130BC545 11 R S T TB6 Terminal block for contactor Illustration 2 21 Terminal Locations D8h with Contactor and Disconnect Options Installation VLT AQUA Drive D Frame Operat...

Page 28: ...0 0 MAINS TERMINAL SECTION D D MAINS TERMINALS R S T 130BC546 10 Illustration 2 22 Terminal Locations D8h with Circuit Breaker Option Installation VLT AQUA Drive D Frame Operating Instructions MG21A20...

Page 29: ...splay 2 4 6 AC Mains Connection Size wiring is based upon the input current of the frequency converter Comply with local and national electrical codes for cable sizes Connect 3 phase AC input power wi...

Page 30: ...ndividual screen conductors The screen coverage i e the physical area of the cable covered by the screen often stated as a percentage value Screen type i e braided or twisted pattern a Aluminium clad...

Page 31: ...5 6 Control Terminal Functions 1 4 2 3 130BA012 11 61 68 69 39 42 50 53 54 55 12 13 18 19 27 29 32 33 20 37 Illustration 2 29 Control Terminal Locations Connector 1 provides four programmable digital...

Page 32: ...og input terminals 53 and 54 can select either voltage 10 to 10 V or current 0 4 20 mA input signals Remove power to the frequency converter before changing switch positions Set switches A53 and A54 t...

Page 33: ...erminal cover supplied with the frequency converter must be installed to maintain the IP20 rating of the enclosure Illustration 2 32 shows both the covered and uncovered terminals 130BC547 10 Illustra...

Page 34: ...CK11CE311N AC 1 525 690 V N75KT7 N160T7 GE CK95BE311N AC 3 N200T7 N400T7 GE CK11CE311N AC 3 Table 2 13 NOTE In applications requiring UL listing when the frequency converter is supplied with a contact...

Page 35: ...flow for cooling EMC considerations Check for proper installation regarding electromagnetic compatibility Environmental consider ations See equipment label for the maximum ambient operating temperatur...

Page 36: ...motor being operated and the minimum and maximum motor speeds Parameter settings recommended are intended for start up and checkout purposes Application settings may vary See 4 1 Local Control Panel f...

Page 37: ...e 11 3 03 Maximum Reference 12 3 41 Ramp 1 Ramp Up Time 13 3 42 Ramp 1 Ramp Down Time 14 3 13 Reference Site Linked to Hand Auto Local Remote This concludes the quick set up procedure Press Status to...

Page 38: ...ming to be completed See 6 Application Examples for application set up information The following procedure is recommended after application set up by the user is completed CAUTION MOTOR START Ensure t...

Page 39: ...e Programming Guide for details on use of the NLCP 4 1 1 LCP Layout The LCP is divided into four functional groups see Illustration 4 1 Auto on Reset Hand on Off Status Quick Menu Main Menu Alarm Log...

Page 40: ...atus Quick Menu Main Menu Alarm Log Illustration 4 4 Key Function Status Shows operational information In Auto mode press to toggle between status read out displays Press repeatedly to scroll through...

Page 41: ...d at the bottom of the LCP 130BP046 10 Hand on Off Auto on Reset Illustration 4 6 Key Function Hand On Starts the frequency converter in local control Use the navigation keys to control frequency conv...

Page 42: ...f the frequency converter Initialisation can be through 14 22 Operation Mode or manually Initialisation using 14 22 Operation Mode does not change frequency converter data such as operating hours seri...

Page 43: ...in open loop using the quick menu This procedure programs the frequency converter to receive a 0 10 V DC analog control signal on input terminal 53 The frequency converter will respond by providing 20...

Page 44: ...erter that the minimum voltage received on terminal 53 0 V equals 20 Hz output 130BT773 11 Q3 21 14 7 0 00 A 1 1 Analog Reference 6 14 Terminal 53 Low Ref Feedb Value 000020 000 Illustration 5 8 10 6...

Page 45: ...minal 18 Digital Input 8 Start 14 7 0 00A 1 1 Digital Inputs Illustration 5 13 5 4 International North American Default Parameter Settings Setting 0 03 Regional Settings 0 International or 1 North Ame...

Page 46: ...requency converter with system details it needs to operate properly System details may include such things as input and output signal types programming terminals minimum and maximum signal ranges cust...

Page 47: ...r Ramps 3 80 Jog Ramp Time 3 81 Quick Stop Ramp Time 3 82 Starting Ramp Up Time 3 9 Digital Pot Meter 3 90 Step Size 3 91 Ramp Time 3 92 Power Restore 3 93 Maximum Limit 3 94 Minimum Limit 3 95 Ramp D...

Page 48: ...tance 12 21 Process Data Config Write 12 22 Process Data Config Read 12 27 Primary Master 12 28 Store Data Values 12 29 Store Always 12 3 EtherNet IP 12 30 Warning Parameter 12 31 Net Reference 12 32...

Page 49: ...ID Start Speed Hz 20 84 On Reference Bandwidth 20 9 PID Controller 20 91 PID Anti Windup 20 93 PID Proportional Gain 20 94 PID Integral Time 20 95 PID Differentiation Time 20 96 PID Diff Gain Limit 21...

Page 50: ...Feedb Value 26 25 Term X42 3 High Ref Feedb Value 26 26 Term X42 3 Filter Time Constant 26 27 Term X42 3 Live Zero 26 3 Analog Input X42 5 26 30 Terminal X42 5 Low Voltage 26 31 Terminal X42 5 High Vo...

Page 51: ...ownloaded to the frequency converter Or the entire frequency converter profile can be loaded onto the PC for back up storage or analysis The USB connector or RS 485 terminal are available for connecti...

Page 52: ...omplete AMA 5 12 Terminal 27 Digital Input 2 Coast inverse Default Value Notes comments Parameter group 1 2 Motor Data must be set according to motor Table 6 1 AMA with T27 Connected Parameters FC 24...

Page 53: ...Terminal 37 Digital Input 1 Safe Stop Alarm Default Value Notes comments If 5 12 Terminal 27 Digital Input is set to 0 No operation a jumper wire to terminal 27 is not needed Table 6 5 Start Stop Comm...

Page 54: ...Notes comments Table 6 8 External Alarm Reset Parameters FC 24 V 24 V D IN D IN D IN COM D IN D IN D IN D IN 10 V A IN A IN COM A OUT COM 12 13 18 19 20 27 29 32 33 37 50 53 54 55 42 39 A53 U I 5k 13...

Page 55: ...rate in the above mentioned parameters Table 6 11 RS 485 Network Connection Parameters FC 24 V 24 V D IN D IN D IN COM D IN D IN D IN D IN 10 V A IN A IN COM A OUT COM 12 13 18 19 20 27 29 32 33 37 50...

Page 56: ...rnal equipment may then indicate that service may be required If the feedback error goes below the limit again within 5 s then the frequency converter continues and the warning disappears But Relay 1...

Page 57: ...e serial communi cation Hand on The frequency converter can be controlled by the navigation keys on the LCP Stop commands reset reversing DC brake and other signals applied to the control terminals ca...

Page 58: ...and speed down Jog request A jog command has been given but the motor will be stopped until a run permissive signal is received via a digital input Jogging The motor is running as programmed in 3 19 J...

Page 59: ...t after the start delay time expires Start fwd rev Start forward and start reverse were selected as functions for two different digital inputs parameter group 5 1 Digital Inputs The motor will start i...

Page 60: ...uency converter logic will continue to operate and monitor the frequency converter status After the fault condition is remedied the frequency converter can be reset It will then be ready to start oper...

Page 61: ...ts Auto on Reset Hand on Off B a c k C a n c e l Info OK On Alarm Warn 130BB467 10 Illustration 8 3 Warn LED Alarm LED Warning ON OFF Alarm OFF ON Flashing Trip Lock ON ON Flashing Table 8 1 Warnings...

Page 62: ...low for cooling EMC considerations Check for proper installation regarding electromagnetic compatibility Environmental consider ations See equipment label for the maximum ambient operating temperature...

Page 63: ...e intermediate circuit voltage DC is lower than the low voltage warning limit The limit is dependent on the frequency converter voltage rating The unit is still active WARNING ALARM 7 DC overvoltage I...

Page 64: ...e limit is exceeded during ramp up extend the ramp up time If the generator torque limit is exceeded during ramp down extend the ramp down time If torque limit occurs while running possibly increase t...

Page 65: ...rake resistance power If 2 Trip is selected in 2 13 Brake Power Monitoring the frequency converter will trip when the dissipated braking power reaches 100 WARNING There is a risk of substantial power...

Page 66: ...tch 1284 Cannot read digital signal processor software version No Text 1299 Option SW in slot A is too old 1300 Option SW in slot B is too old 1301 Option SW in slot C0 is too old 1302 Option SW in sl...

Page 67: ...rd Check for a defective control card If an option card is present check for an overvoltage condition WARNING 49 Speed limit When the speed is not within the specified range in 4 11 Motor Speed Low Li...

Page 68: ...too warm Normal operation can be resumed when the MCB 112 applies 24 V DC to T37 again when the motor temperature reaches an acceptable level and when the Digital Input from the MCB 112 is deactivate...

Page 69: ...verter for normal operation WARNING 251 New typecode The power card or other components have been replaced and the typecode changed Reset to remove the warning and resume normal operation Warnings and...

Page 70: ...g Check the wiring for shorts or incorrect connections If the display continues to cut out follow the procedure for display dark Motor not running Service switch open or missing motor connection Check...

Page 71: ...s Check ramp time settings Check parameter group 2 0 DC Brake and 3 0 Reference Limits Open power fuses or circuit breaker trip Phase to phase short Motor or panel has a short phase to phase Check mot...

Page 72: ...arameter group 4 6 Speed Bypass Check if noise and or vibration have been reduced to an acceptable limit Turn off over modulation in 14 03 Overmodulation Change switching pattern and frequency in para...

Page 73: ...2 397 487 588 Continuous kVA at 400 V kVA 147 180 218 274 333 407 Continuous kVA at 460 V kVA 151 191 241 288 353 426 Max Input current Continuous at 400 V A 204 251 304 381 381 463 463 567 Continuous...

Page 74: ...130 154 191 241 Continuous kVA at 690 V kVA 103 129 157 185 229 289 Max Input current Continuous at 550 V A 89 110 130 158 198 245 Continuous at 575 V A 85 106 124 151 189 234 Continuous at 690 V A 8...

Page 75: ...3848 4610 5150 Weight enclosure IP21 IP54 kg lbs 125 275 Weight enclosure IP20 kg lbs 125 275 Efficiency 0 98 Output frequency 0 590 Hz Heatsink overtemp trip 110 C Power card ambient trip 75 C Normal...

Page 76: ...Torque Characteristics Starting torque Constant torque maximum 110 for 60 s Starting torque maximum 135 up to 0 5 s Overload torque Constant torque maximum 110 for 60 s Percentage relates to the freq...

Page 77: ...driven Max frequency at terminal 29 33 5 kHz open collector Min frequency at terminal 29 33 4 Hz Voltage level see 10 2 1 Digital Inputs Maximum voltage on input 28 V DC Input resistance Ri approx 4...

Page 78: ...V AC 0 2 A Max terminal load DC 1 1 on 1 3 NC Resistive load 50 V DC 2 A Max terminal load DC 13 1 on 1 3 NC Inductive load 24 V DC 0 1 A Min terminal load on 1 3 NC 1 2 NO 24 V DC 10 mA 24V AC 2 mA...

Page 79: ...tion 0 C Minimum ambient temperature at reduced performance 10 C Temperature during storage transport 25 to 65 70 C Maximum altitude above sea level without derating 1000 m Maximum altitude above sea...

Page 80: ...auto derating function to avoid its heatsink reaching 95 C The frequency converter is protected against short circuits on motor terminals U V W If a mains phase is missing the frequency converter tri...

Page 81: ...75K N400 525 690 V type aR Table 10 5 Power Size Fuse options Bussman PN Littelfuse PN Littelfuse PN Bussmann PN Siba PN Ferraz Shawmut PN Ferraz Shawmut PN Europe Ferraz Shawmut PN North America N110...

Page 82: ...as follows 415 V IEC1 480 V UL2 600 V UL2 690 V IEC1 D6h frame 100 000 A 100 000 A 100 000 A 100 000 A D8h frame not including the N315T4 100 000 A 100 000 A 100 000 A 100 000 A D8h frame N315T4 only...

Page 83: ...28 Terminals 33 38 54 42 29 Wiring 10 12 13 32 59 Wiring Connection 27 Cooling Cooling 8 Clearance 32 59 Copying Parameter Settings 38 Current Limit 34 Rating 8 60 D DC Current 6 54 Link 60 Derating...

Page 84: ...nstallation 8 Menu Keys 36 37 Structure 38 43 Motor Cable 26 Cables 12 14 Connection 14 Current 6 64 37 Data 33 34 61 64 Frequency 37 Output U V W 73 Power 12 64 37 Protection 12 77 Rotation 37 Rotati...

Page 85: ...e 29 35 40 54 49 Start Up 5 39 40 67 Status Messages 54 Mode 54 Stop Command 54 Supply Voltage 27 28 63 74 Surroundings 76 Switching Frequency 54 System Feedback 6 T Temperature Limits 32 59 Terminal...

Page 86: ...www danfoss com drives MG21A202 130R0289 MG21A202 Rev 2012 06 15...

Page 87: ......

Reviews: