4.
Press the navigation keys to scroll to
0-03 Regional Settings
and press [OK].
0-0
*
Basic Settings
0.0%
0-03 Regional Settings
[0] International
0.00A
1(1)
130BP088.10
Illustration 3.3
5.
Press the navigation keys to select
International
or
North America
as appropriate and press [OK].
(This changes the default settings for a number
of basic parameters. See
for a complete list.)
6.
Press [Quick Menu] on the LCP.
7.
Press the navigation keys to scroll to parameter
group
Q2 Quick Setup
and press [OK].
130BB847.10
Q1 My Personal Menu
Q2 Quick Setup
Q5 Changes Made
Q6 Loggings
13.7% 13.0A 1(1)
Quick Menus
Illustration 3.4
8.
Select language and press [OK]. Then enter the
motor data in
1-20 Motor Power [kW]
/
1-21 Motor
Power [HP]
to
1-25 Motor Nominal Speed
. The
information can be found on the motor
nameplate.
•
1-20 Motor Power [kW]
or
1-21 Motor
Power [HP]
•
1-22 Motor Voltage
•
1-23 Motor Frequency
•
1-24 Motor Current
•
1-25 Motor Nominal Speed
130B
T772.10
Q2
0.0 Hz 0.00kW 1(1)
Motor Setup
1 - 21 Motor Power [kW]
4.0
kW
Illustration 3.5
9.
A jumper wire should be in place between
control terminals 12 and 27. If this is the case,
leave
5-12 Terminal 27 Digital Input
at factory
default. Otherwise select
No Operation
. For
frequency converters with an optional bypass, no
jumper wire is required.
10.
3-02 Minimum Reference
11.
3-03 Maximum Reference
12.
3-41 Ramp 1 Ramp Up Time
13.
3-42 Ramp 1 Ramp Down Time
14.
3-13 Reference Site
. Linked to Hand/Auto* Local
Remote.
This concludes the quick set-up procedure. Press [Status]
to return to the operational display.
3.4 Local-control Test
CAUTION
MOTOR START!
Ensure that the motor, system and any attached
equipment are ready for start. It is the responsibility of the
user to ensure safe operation under any condition. Failure
to ensure that the motor, system, and any attached
equipment is ready for start could result in personal injury
or equipment damage.
NOTE
The [Hand On] key provides a local start command to the
frequency converter. The [Off] key provides the stop
function.
When operating in local mode, [
▲
] and [
▼
] increase and
decrease the speed output of the frequency converter. [
◄
]
and [
►
] move the display cursor in the numeric display.
1.
Press [Hand On].
2.
Accelerate the frequency converter by pressing
[
▲
] to full speed. Moving the cursor left of the
decimal point provides quicker input changes.
3.
Note any acceleration problems.
4.
Press [Off].
5.
Note any deceleration problems.
If acceleration problems were encountered
•
If warnings or alarms occur, see
•
Check that motor data is entered correctly
•
Increase the ramp-up time accel time in
3-41 Ramp 1 Ramp Up Time
•
Increase current limit in
4-18 Current Limit
•
Increase torque limit in
4-16 Torque Limit Motor
Mode
Start Up and Commissioning