The control unit attempts to correct the ramp if possible.
The inverter turns off to protect the transistors
and the intermediate circuit capacitors when a
certain voltage level is reached.
Mains drop-out
During a mains drop-out, VLT 7000 Booster continues
until the intermediate circuit voltage drops below the
minimum stop level, which is typically 15% below VLT
7000 Booster
’
s lowest rated supply voltage.
The time before the inverter stops depends on the mains
voltage before the drop-out and on the motor load.
Static overload
When VLT 7000 Booster is overloaded (the current
limit in parameter 215
Current limit
, I
LIM
has been
reached), the controls will reduce the output frequency
in an attempt to reduce the load.
If the overload is excessive, a current may
occur that makes the frequency converter cut
out after approx. 1.5 sec.
Operation within the current limit can be limited in time
(0-60 s) in parameter 412
Trip delay overcurrent, I
LIM
.