VLT® 7000 Booster
■
Technical data, mains supply 3 x 380-460V
According to international requirements
VLT type
7002
7003
7004
7005
7006
7008
7011
Output current
I
VLT,N
[A] (380-440
V)
3.0
4.1
5.6
7.2
10.0
13.0
16.0
I
VLT, MAX
(60 s) [A]
(380-440 V)
3.3
4.5
6.2
7.9
11.0
14.3
17.6
I
VLT, N
[A] (441-460
V)
3.0
3.4
4.8
6.3
8.2
11.0
14.0
I
VLT, MAX
(60 s) [A]
(441-460 V)
3.3
3.7
5.3
6.9
9.0
12.1
15.4
Output power
S
VLT,N
[kVA] (400 V)
2.2
2.9
4.0
5.2
7.2
9.3
11.5
S
VLT,N
[kVA] (460 V)
2.4
2.7
3.8
5.0
6.5
8.8
11.2
Typical shaft
output
P
VLT,N
[kW]
1.1
1.5
2.2
3.0
4.0
5.5
7.5
Typical shaft
output
P
VLT,N
[HP]
1.5
2
3
-
5
7.5
10
Max.
cable
cross-section to
motor
[mm
2
]/[AWG]
2) 4)
4/10
4/10
4/10
4/10
4/10
4/10
4/10
Max.
input
current
I
L,N
[A] (380 V)
2.8
3.8
5.3
7.0
9.1
12.2
15.0
(RMS)
I
L,N
[A] (460 V)
2.5
3.4
4.8
6.0
8.3
10.6
14.0
Max. cable
cross-section
power
[mm
2
]/[AWG]
2) 4)
4/10
4/10
4/10
4/10
4/10
4/10
4/10
Max. pre-fuses
[-]/UL
1)
[A]
16/6
16/10
16/10
16/15
25/20
25/25
35/30
Mains contactor
[Danfoss type]
CI 6
CI 6
CI 6
CI 6
CI 6
CI 6
CI 6
Efficiency
3)
0.96
0.96
0.96
0.96
0.96
0.96
0.96
Weight IP 20
[kg]
8
8
8.5
8.5
10.5
10.5
10.5
Power loss at
max. load. [W]
Total
67
92
110
139
198
250
295
Enclosure
VLT type
IP 20
1. For type of fuse, see section
Fuses
.
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Max. cable cross section is the maximum possible cable cross section that can be fitted on the terminals.
Always comply with national and local regulations on min. cable cross-section.