   VLT

® 

6000 HVAC

6

MG.60.G2.02 - VLT is a registered Danfoss Trademark

The CANCEL key is used if a change of

the selected parameter is not to be

carried out.

The OK key is used to activate a

change to the selected parameter.

The + and - keys are used to scroll

through parameters and to increase or

decrease the value of a chosen

parameter. The keys are also used to

change the local reference. In Display

Mode, the keys are used to switch

between readouts.

The

 

t

 and 

u

 keys are used to select a

parameter group and also to move the

cursor to the desired digit when

changing numerical values.

Local Control

Start signal via digital inputs may cause

drive to start at any time. Remove power

to drive before working on output wiring,

motor or any driven equipment.

Below the indicator lamps on the LCP are keys

used to determine control of the drive. Each key can

be individually enabled or disabled using parameters

012 through 015. The Hand Start and Auto Start

keys are disabled if any of the control terminals are

programmed for either Remote Hand or Remote

Auto.

The HAND START key is used to start

the drive from the control panel.

Pressing HAND START issues a start

command to the drive.

If a minimum speed is set in parameter

201, 

Output Frequency Low Limit

, motor

will start and ramp up to this frequency

when HAND START key is pressed. If drive is already

running in Auto Mode when HAND START is

pressed, drive will begin running in Hand Mode and in

local control.

The OFF/STOP key is used for

stopping the connected motor in either

the Hand or Auto Mode. Enable or

disable this function via parameter 013,

OFF/START on LCP

. If this stop

function is activated, the second line in

the LCD display will flash.

AUTO START is used if the drive is to

be started via FLN serial communi-

cation and/or the digital control

terminals. When a remote start signal

is received, the drive will start if the

AUTO START key has been pressed.

NOTE:

NOTE:

NOTE:

NOTE:

NOTE:

AUTO START key must be pressed to

enable starting drive from FLN serial bus or

remote terminals.

RESET is used for manually

resetting the drive after an alarm

(fault trip). In this case, the top line of

the  display shows TRIP (RESET). If

the top line of the display shows TRIP

(AUTO START), the drive will automa-

tically restart. If the top line of the display

shows TRIPLOCK (DICS.MAINS), input

power to the drive must be removed

before the trip can be reset.

.

Quick Menu

The QUICK MENU key gives access to 12 of the

most important setup parameters of the drive. After

Quick Menu programming, in many cases the drive

will be ready for operation. The 12 Quick Menu

parameters are shown in Table 1. Refer to the 

VLT

6000 Operating Instructions

 for a complete

description of the functions.

Summary of Contents for VLT 6000 series

Page 1: ...Parameter Data 7 Extended Menu 8 HP kW 8 VLT 6000 Functional Features Drive Operation 8 Motor and Drive Thermal Protection 8 Set up 1 4 8 Current Monitoring and Limits 9 Direction of Rotation 9 Start...

Page 2: ...g Input Monitoring 15 Drive Relay Control 15 Network Connection Hardware Setup 16 Electrical Control Terminals 17 Typical Control Connection Examples 18 VLT 6000 Functional Features Startup of FLN Man...

Page 3: ...Guidelines 1 The drive must be disconnected from the AC line before any service work is done 2 The Stop Off key on the local control panel of the drive does not disconnect the equip ment from the AC l...

Page 4: ...t has been disconnected from AC line To be sure that capacitors have fully discharged wait 14 minutes for 220 and 500 V units and 30 minutes for 550 600 V units after power has been removed before tou...

Page 5: ...is a Siemens registered trademark VLT is a Danfoss registered trademark The VLT 6000 frequency converter is delivered for installation and setup with the required applica tion parameters already progr...

Page 6: ...will start and ramp up to this frequency when HAND START key is pressed If drive is already running in Auto Mode when HAND START is pressed drive will begin running in Hand Mode and in local control...

Page 7: ...Press key once to change hundreds digit to 1 6 Press u key once to move cursor to tens digit Quick Menu Item Number Parameter Name Description 1 001 Language Selects language used for all displays 2 1...

Page 8: ...are the system status what the motor and drive are doing and if there are any problems The VLT 6000 continuously monitors all aspects of motor and drive status and issues alarms or warnings for advers...

Page 9: ...incapable of stopping the drive The serial interface continues to access drive settings Hand Auto Modes 34 The SEL HND AUTO shows which mode the drive is in The drive can be commanded into either Han...

Page 10: ...ENS SIEMENS SIEMENS SIEMENS DANFOSS DANFOSS DANFOSS DANFOSS GAIN GAIN GAIN GAIN I II I GAIN GAIN GAIN GAIN P P P P TIME TIME TIME TIME PI PI PI PI 667 667 667 667 GAIN GAIN GAIN GAIN P P P P GAIN GAIN...

Page 11: ...oller This can be turned on or off depending on the requirements of the control strategy A brief summary of possibilities follows This is meant to illustrate possibilities rather than be all inclusive...

Page 12: ...the drive will shut off immediately and the motor will coast to a stop When set to COAST the lower right corner of the drive display shows UN READY unit ready The drive will not start in either HAND...

Page 13: ...ls from the FLN The FLN receives the feedback signal from the controlled system It sends this and the desired setpoint to the VLT 6000 PID controller The drive compares the feedback signal with the se...

Page 14: ...oint 51 or parameter 205 If an attempt is made to set point 69 to a value outside of this range the setpoint will not be changed SETPOINT 1 can also be programmed using parameter 418 Setpoint 1 7 0 7...

Page 15: ...in the VLT 6000 usually provide drive status indications these indications are generally not needed when the drive is connected to an FLN In some applications it can be useful to have the FLN control...

Page 16: ...ply from the common of the digital inputs Normally this switch is ON and the power supply is present at terminals 12 and 13 for digital inputs When OFF the negative of an external power supply is conn...

Page 17: ...t is 200 mA 16 33 Digital inputs R 2 kohm 5 V logical 0 10 V logical 1 16 33 30 VAC 42 5 VDC 1 A relay output can be used for indicating status and warnings 20 Voltage supply to digital inputs and ext...

Page 18: ...ur Figur Figur Figure 6 e 6 e 6 e 6 e 6 Two Feedback Signals Connection T T T T Transmitter Connection ransmitter Connection ransmitter Connection ransmitter Connection ransmitter Connection The drive...

Page 19: ...e Interval and 566 FLN Time Interval Function can be commanded by the data points 36 and 37 see Table 9 NOTE NOTE NOTE NOTE NOTE Drive can store preset references programmed in parameters 211 through...

Page 20: ...T 6000 LCP keypad Drive operation can then be controlled through the host network device in accordance with its operation instructions NOTE NOTE NOTE NOTE NOTE Default setting for point number 35 Run...

Page 21: ...tage low X 7 Over voltage X X 8 Under voltage X X 9 Inverter time X X 10 Motor time X X 11 Motor thermistor X X 12 Current limit X X 13 Over current X X 14 Ground fault X X 15 Switch mode fault X X 16...

Page 22: ...eadout Points 03 FREQ OUTPUT 0 HZ 0 1 0 16383 R 512 LAI 06 CURRENT 0 A 0 1 0 16383 R 514 LAI 08 POWER 0 KW 1 0 511 R 515 LAI 10 KWH 0 KWH 3 1 0 32767 R 602 LAI 12 RUN TIME 0 HRS 4 0 0 32767 R 601 LAI...

Page 23: ...R 204 LAI 49 REF MAX S Note 4 UNIT 0 1 1638 3 32767 R 205 LAI Setpoint Related Points 50 REF MIN Note 3 0 UNIT 0 1 1638 3 32767 W 204 LAO 51 REF MAX Note 3 Note 4 UNIT 0 1 1638 3 32767 W 205 LAO 52 RE...

Page 24: ...NOTENA ENABLE NOTENA R 527 2 LDI 81 DRV RDY STAT NOTRDY READY NOTRDY R 527 1 LDI 82 DRVCTRL STAT NOTRDY READY NOTRDY R 527 0 LDI 84 RESET NO RESET NO R 530 7 LDI 85 START OFF ON OFF R 530 6 LDI 86 Q...

Page 25: ...n vary depending on settings of other points or the drive size Consult the VLT 6000 Operating Instructions for values Twelve special read only points can be used for checking if the value actually cha...

Page 26: ...s been given a coast to stop command 28 CMD COAST Commands drive to make motor coast to a stop 29 DAY NIGHT Selects day or night mode Has no effect on drive operation 30 CURRENT LIM Sets maximum drive...

Page 27: ...er 415 73 BUS FB 1 Supplies feedback value for bus feedback 1 in percent 74 BUS FB 2 Supplies feedback value for bus feedback 2 in percent 75 AUTO RAMP Displays when drive deceleration rate is extende...

Reviews: