Danfoss VLT 6000 series Manual Download Page 4

   VLT

® 

6000 HVAC

4

MG.60.G2.02 - VLT is a registered Danfoss Trademark

About This Manual

The documentation in this manual provides

comprehensive information on the connection,

programming, and start-up of the VLT 6000 for

use with the FLN. It is intended as both an instruc-

tion and reference manual. Functions and features

of the VLT 6000 frequency converter are also

briefly reviewed to serve as a guideline to optimize

your communication system. Read this manual

before programming since important information is

provided in each section.

For detailed information on using the VLT 6000, see

the 

VLT 6000 Operating Instructions.

Assumptions

This manual assumes that the controller node

supports the interfaces in this document and that

all the requirements and limitations stipulated in the

controller node and the VLT 6000 are strictly ob-

served. It is assumed that the user understands

the general capabilities and limitation of the con-

troller node and the VLT 6000 Frequency Converter.

References

Installation, Operation and Maintenance Manual

for the VLT 6000 Frequency Converter

,

Danfoss Graham document 23-6108-00.

(Referred to as the 

VLT 6000 Operating Instructions

in this manual.)

Operating Instructions VLT 6000 HVAC Frequency

Converter

, Danfoss document MG.60.AX.YY

(International version of the 

VLT 6000 Operating

Instructions.

)

Contact Siemens for operational instructions for the

Floor Level Network.

■ 

■ 

■ 

■ 

■ 

Introduction

Touching electrical parts may be fatal - even after equipment
has been disconnected from AC line. To be sure that
capacitors have fully discharged, wait 14 minutes for 220
and 500 V units and 30 minutes for 550-600 V units after
power has been removed before touching any internal
component.

DANGER:

The Siemens Floor Level Network (FLN) is a master/

slave control network for serial communication with

various control devices. The FLN controller is RS-

485 compatible, half duplex, with an operating rate

of 4800 or 9600 baud. Recommended wiring is

shielded, twisted pair. The FLN software protocol is

designed to be general in nature to accommodate

any unique properties of each device type. The node

address system allows up to 96 devices to be used

on any one system.

The Danfoss VLT 6000 is a programmable frequency

converter which controls the operation of 3-phase,

standard induction electrical motors in the HVAC

industry. The VLT 6000 controller has FLN

communication protocol software built-in. The drive

uses optical isolation for fault tolerance and noise

immunity.

The FLN communicates directly with the VLT 6000

drive via the RS-485 serial interface bus. In addition

to being able to control the drive, most drive confi-

guration and control parameters can be reviewed

and changed through the FLN. Also, the operatio-

nal status of the drive can be read and monitored

through the bus. Diagnostic and operational infor-

mation stored in the VLT 6000 is easily available,

such as kWh of energy used, total operation hours,

drive status, motor speed, and many other useful

items which can be accessed and monitored

through the FLN.

The FLN is designed to communicate with any

controller node that supports the interfaces defined

in this document.

Summary of Contents for VLT 6000 series

Page 1: ...Parameter Data 7 Extended Menu 8 HP kW 8 VLT 6000 Functional Features Drive Operation 8 Motor and Drive Thermal Protection 8 Set up 1 4 8 Current Monitoring and Limits 9 Direction of Rotation 9 Start...

Page 2: ...g Input Monitoring 15 Drive Relay Control 15 Network Connection Hardware Setup 16 Electrical Control Terminals 17 Typical Control Connection Examples 18 VLT 6000 Functional Features Startup of FLN Man...

Page 3: ...Guidelines 1 The drive must be disconnected from the AC line before any service work is done 2 The Stop Off key on the local control panel of the drive does not disconnect the equip ment from the AC l...

Page 4: ...t has been disconnected from AC line To be sure that capacitors have fully discharged wait 14 minutes for 220 and 500 V units and 30 minutes for 550 600 V units after power has been removed before tou...

Page 5: ...is a Siemens registered trademark VLT is a Danfoss registered trademark The VLT 6000 frequency converter is delivered for installation and setup with the required applica tion parameters already progr...

Page 6: ...will start and ramp up to this frequency when HAND START key is pressed If drive is already running in Auto Mode when HAND START is pressed drive will begin running in Hand Mode and in local control...

Page 7: ...Press key once to change hundreds digit to 1 6 Press u key once to move cursor to tens digit Quick Menu Item Number Parameter Name Description 1 001 Language Selects language used for all displays 2 1...

Page 8: ...are the system status what the motor and drive are doing and if there are any problems The VLT 6000 continuously monitors all aspects of motor and drive status and issues alarms or warnings for advers...

Page 9: ...incapable of stopping the drive The serial interface continues to access drive settings Hand Auto Modes 34 The SEL HND AUTO shows which mode the drive is in The drive can be commanded into either Han...

Page 10: ...ENS SIEMENS SIEMENS SIEMENS DANFOSS DANFOSS DANFOSS DANFOSS GAIN GAIN GAIN GAIN I II I GAIN GAIN GAIN GAIN P P P P TIME TIME TIME TIME PI PI PI PI 667 667 667 667 GAIN GAIN GAIN GAIN P P P P GAIN GAIN...

Page 11: ...oller This can be turned on or off depending on the requirements of the control strategy A brief summary of possibilities follows This is meant to illustrate possibilities rather than be all inclusive...

Page 12: ...the drive will shut off immediately and the motor will coast to a stop When set to COAST the lower right corner of the drive display shows UN READY unit ready The drive will not start in either HAND...

Page 13: ...ls from the FLN The FLN receives the feedback signal from the controlled system It sends this and the desired setpoint to the VLT 6000 PID controller The drive compares the feedback signal with the se...

Page 14: ...oint 51 or parameter 205 If an attempt is made to set point 69 to a value outside of this range the setpoint will not be changed SETPOINT 1 can also be programmed using parameter 418 Setpoint 1 7 0 7...

Page 15: ...in the VLT 6000 usually provide drive status indications these indications are generally not needed when the drive is connected to an FLN In some applications it can be useful to have the FLN control...

Page 16: ...ply from the common of the digital inputs Normally this switch is ON and the power supply is present at terminals 12 and 13 for digital inputs When OFF the negative of an external power supply is conn...

Page 17: ...t is 200 mA 16 33 Digital inputs R 2 kohm 5 V logical 0 10 V logical 1 16 33 30 VAC 42 5 VDC 1 A relay output can be used for indicating status and warnings 20 Voltage supply to digital inputs and ext...

Page 18: ...ur Figur Figur Figure 6 e 6 e 6 e 6 e 6 Two Feedback Signals Connection T T T T Transmitter Connection ransmitter Connection ransmitter Connection ransmitter Connection ransmitter Connection The drive...

Page 19: ...e Interval and 566 FLN Time Interval Function can be commanded by the data points 36 and 37 see Table 9 NOTE NOTE NOTE NOTE NOTE Drive can store preset references programmed in parameters 211 through...

Page 20: ...T 6000 LCP keypad Drive operation can then be controlled through the host network device in accordance with its operation instructions NOTE NOTE NOTE NOTE NOTE Default setting for point number 35 Run...

Page 21: ...tage low X 7 Over voltage X X 8 Under voltage X X 9 Inverter time X X 10 Motor time X X 11 Motor thermistor X X 12 Current limit X X 13 Over current X X 14 Ground fault X X 15 Switch mode fault X X 16...

Page 22: ...eadout Points 03 FREQ OUTPUT 0 HZ 0 1 0 16383 R 512 LAI 06 CURRENT 0 A 0 1 0 16383 R 514 LAI 08 POWER 0 KW 1 0 511 R 515 LAI 10 KWH 0 KWH 3 1 0 32767 R 602 LAI 12 RUN TIME 0 HRS 4 0 0 32767 R 601 LAI...

Page 23: ...R 204 LAI 49 REF MAX S Note 4 UNIT 0 1 1638 3 32767 R 205 LAI Setpoint Related Points 50 REF MIN Note 3 0 UNIT 0 1 1638 3 32767 W 204 LAO 51 REF MAX Note 3 Note 4 UNIT 0 1 1638 3 32767 W 205 LAO 52 RE...

Page 24: ...NOTENA ENABLE NOTENA R 527 2 LDI 81 DRV RDY STAT NOTRDY READY NOTRDY R 527 1 LDI 82 DRVCTRL STAT NOTRDY READY NOTRDY R 527 0 LDI 84 RESET NO RESET NO R 530 7 LDI 85 START OFF ON OFF R 530 6 LDI 86 Q...

Page 25: ...n vary depending on settings of other points or the drive size Consult the VLT 6000 Operating Instructions for values Twelve special read only points can be used for checking if the value actually cha...

Page 26: ...s been given a coast to stop command 28 CMD COAST Commands drive to make motor coast to a stop 29 DAY NIGHT Selects day or night mode Has no effect on drive operation 30 CURRENT LIM Sets maximum drive...

Page 27: ...er 415 73 BUS FB 1 Supplies feedback value for bus feedback 1 in percent 74 BUS FB 2 Supplies feedback value for bus feedback 2 in percent 75 AUTO RAMP Displays when drive deceleration rate is extende...

Reviews: