background image

   VLT

® 

6000 HVAC

10

MG.60.G2.02 - VLT is a registered Danfoss Trademark

PID Control Functions (42, 61-65, 68-74)

The VLT 6000 has a sophisticated built-in propor-

tional, integral, derivative (PID) controller. The PID

controller is activated by setting parameter 100,

Configuration

, to 

Closed loop

 through the drive’s

keypad.

The PID controller in the VLT 6000 supports two

feedback values and two setpoints. The feedback

can be received in the form of network bus signals

and/or standard 0-10 V transmitters. The 2 setpoint

controller is capable of controlling return fans based

on a fixed differential flow, secondary pumping

systems, and so on. This can be used to supple-

ment the BMS system to save on points or ca-

pacity.  For details on use of the two feedback/

setpoint feature, refer to the

 VLT 6000 Operating

Instructions

. Data points 43 and 44 show the status

of an FLN command to the drive.

The points PI GAIN and PI TIME are gain

parameters similar to the P and I gains in the FLN

TECs. The Danfoss PI loop is structured differently

than the Siemens loop, so there is not a one-to-one

correspondence between the gains. The following

formulas allow translation between Danfoss and

Siemens gains.

Converting from Danfoss PI gains to Siemens P and

I gains:

0.0015

0.0015

0.0015

0.0015

****

 TIME

 TIME

 TIME

 TIME

PI

PI

PI

PI

    

GAIN

GAIN

GAIN

GAIN

    

PI

PI

PI

PI

    

GAIN

GAIN

GAIN

GAIN

    

IIII

0.0015

0.0015

0.0015

0.0015

****

GAIN

GAIN

GAIN

GAIN

    

PI

PI

PI

PI

GAIN

GAIN

GAIN

GAIN

    

P

P

P

P

    

    

DANFOSS

DANFOSS

DANFOSS

DANFOSS

    

DANFOSS

DANFOSS

DANFOSS

DANFOSS

SIEMENS

SIEMENS

SIEMENS

SIEMENS

DANFOSS

DANFOSS

DANFOSS

DANFOSS

SIEMENS

SIEMENS

SIEMENS

SIEMENS

=

=

SIEMENS

SIEMENS

SIEMENS

SIEMENS

SIEMENS

SIEMENS

SIEMENS

SIEMENS

DANFOSS

DANFOSS

DANFOSS

DANFOSS

SIEMENS

SIEMENS

SIEMENS

SIEMENS

DANFOSS

DANFOSS

DANFOSS

DANFOSS

    

GAIN

GAIN

GAIN

GAIN

    I

III

    

GAIN

GAIN

GAIN

GAIN

    

P

P

P

P

 TIME 

 TIME 

 TIME 

 TIME 

PI

PI

PI

PI

667

667

667

667

****

GAIN

GAIN

GAIN

GAIN

    

P

P

P

P

GAIN

GAIN

GAIN

GAIN

    

PI

PI

PI

PI

    

    

=

=

Sleep Mode (54-59)

Sleep mode automatically stops the drive when

demand is low over a period of time. When the

system demand increases, the drive restarts the

motor to reach the desired output. Sleep mode has

great energy savings potential and saves wear and

tear on equipment. Unlike a setback timer, the drive

is always available to run when a preset “wakeup”

demand is reached. See parameters 403 through

406 in the 

VLT 6000 Operating Instructions

 for more

detail.

Drive Control Display (80-86)

The operational status of the drive is readily available

on the FLN serial interface bus. The drive displays

various states including ready to start, waiting for

run enable, run, fault reset and stop.

Terminals 53, 54, 60 (87-89)

Two analog voltage input terminals 53 and 54 (0 to

10 VDC) and one analog current terminal 60 (0 to

20 mA) are provided for reference or feedback

signals.  The applied electrical signal can be read by

data points 87 to 89 in volts and mA. This can be

very useful during commissioning to calibrate

transmitters. This can also be used to convert any

other analog transmitter in the installation into a

digital bus signal, even if the signal is not used by

the drive. In this case, the input terminal should be

programmed to 

No Function

 so it does not to

influence the drive’s operation.

Faults, Warnings and Alarms (90-94)

The drive displays a warning or tripped by a fault

condition. It also can retrieve the last warning or

fault trip for display. The drive can be reset through

the FLN serial bus to resume normal drive operation.

Error Status (99)

Data point 99 is implemented in the point map but is

not used in this application.

Converting from Siemens P and I gains to

Danfoss PI gains:

Summary of Contents for VLT 6000 series

Page 1: ...Parameter Data 7 Extended Menu 8 HP kW 8 VLT 6000 Functional Features Drive Operation 8 Motor and Drive Thermal Protection 8 Set up 1 4 8 Current Monitoring and Limits 9 Direction of Rotation 9 Start...

Page 2: ...g Input Monitoring 15 Drive Relay Control 15 Network Connection Hardware Setup 16 Electrical Control Terminals 17 Typical Control Connection Examples 18 VLT 6000 Functional Features Startup of FLN Man...

Page 3: ...Guidelines 1 The drive must be disconnected from the AC line before any service work is done 2 The Stop Off key on the local control panel of the drive does not disconnect the equip ment from the AC l...

Page 4: ...t has been disconnected from AC line To be sure that capacitors have fully discharged wait 14 minutes for 220 and 500 V units and 30 minutes for 550 600 V units after power has been removed before tou...

Page 5: ...is a Siemens registered trademark VLT is a Danfoss registered trademark The VLT 6000 frequency converter is delivered for installation and setup with the required applica tion parameters already progr...

Page 6: ...will start and ramp up to this frequency when HAND START key is pressed If drive is already running in Auto Mode when HAND START is pressed drive will begin running in Hand Mode and in local control...

Page 7: ...Press key once to change hundreds digit to 1 6 Press u key once to move cursor to tens digit Quick Menu Item Number Parameter Name Description 1 001 Language Selects language used for all displays 2 1...

Page 8: ...are the system status what the motor and drive are doing and if there are any problems The VLT 6000 continuously monitors all aspects of motor and drive status and issues alarms or warnings for advers...

Page 9: ...incapable of stopping the drive The serial interface continues to access drive settings Hand Auto Modes 34 The SEL HND AUTO shows which mode the drive is in The drive can be commanded into either Han...

Page 10: ...ENS SIEMENS SIEMENS SIEMENS DANFOSS DANFOSS DANFOSS DANFOSS GAIN GAIN GAIN GAIN I II I GAIN GAIN GAIN GAIN P P P P TIME TIME TIME TIME PI PI PI PI 667 667 667 667 GAIN GAIN GAIN GAIN P P P P GAIN GAIN...

Page 11: ...oller This can be turned on or off depending on the requirements of the control strategy A brief summary of possibilities follows This is meant to illustrate possibilities rather than be all inclusive...

Page 12: ...the drive will shut off immediately and the motor will coast to a stop When set to COAST the lower right corner of the drive display shows UN READY unit ready The drive will not start in either HAND...

Page 13: ...ls from the FLN The FLN receives the feedback signal from the controlled system It sends this and the desired setpoint to the VLT 6000 PID controller The drive compares the feedback signal with the se...

Page 14: ...oint 51 or parameter 205 If an attempt is made to set point 69 to a value outside of this range the setpoint will not be changed SETPOINT 1 can also be programmed using parameter 418 Setpoint 1 7 0 7...

Page 15: ...in the VLT 6000 usually provide drive status indications these indications are generally not needed when the drive is connected to an FLN In some applications it can be useful to have the FLN control...

Page 16: ...ply from the common of the digital inputs Normally this switch is ON and the power supply is present at terminals 12 and 13 for digital inputs When OFF the negative of an external power supply is conn...

Page 17: ...t is 200 mA 16 33 Digital inputs R 2 kohm 5 V logical 0 10 V logical 1 16 33 30 VAC 42 5 VDC 1 A relay output can be used for indicating status and warnings 20 Voltage supply to digital inputs and ext...

Page 18: ...ur Figur Figur Figure 6 e 6 e 6 e 6 e 6 Two Feedback Signals Connection T T T T Transmitter Connection ransmitter Connection ransmitter Connection ransmitter Connection ransmitter Connection The drive...

Page 19: ...e Interval and 566 FLN Time Interval Function can be commanded by the data points 36 and 37 see Table 9 NOTE NOTE NOTE NOTE NOTE Drive can store preset references programmed in parameters 211 through...

Page 20: ...T 6000 LCP keypad Drive operation can then be controlled through the host network device in accordance with its operation instructions NOTE NOTE NOTE NOTE NOTE Default setting for point number 35 Run...

Page 21: ...tage low X 7 Over voltage X X 8 Under voltage X X 9 Inverter time X X 10 Motor time X X 11 Motor thermistor X X 12 Current limit X X 13 Over current X X 14 Ground fault X X 15 Switch mode fault X X 16...

Page 22: ...eadout Points 03 FREQ OUTPUT 0 HZ 0 1 0 16383 R 512 LAI 06 CURRENT 0 A 0 1 0 16383 R 514 LAI 08 POWER 0 KW 1 0 511 R 515 LAI 10 KWH 0 KWH 3 1 0 32767 R 602 LAI 12 RUN TIME 0 HRS 4 0 0 32767 R 601 LAI...

Page 23: ...R 204 LAI 49 REF MAX S Note 4 UNIT 0 1 1638 3 32767 R 205 LAI Setpoint Related Points 50 REF MIN Note 3 0 UNIT 0 1 1638 3 32767 W 204 LAO 51 REF MAX Note 3 Note 4 UNIT 0 1 1638 3 32767 W 205 LAO 52 RE...

Page 24: ...NOTENA ENABLE NOTENA R 527 2 LDI 81 DRV RDY STAT NOTRDY READY NOTRDY R 527 1 LDI 82 DRVCTRL STAT NOTRDY READY NOTRDY R 527 0 LDI 84 RESET NO RESET NO R 530 7 LDI 85 START OFF ON OFF R 530 6 LDI 86 Q...

Page 25: ...n vary depending on settings of other points or the drive size Consult the VLT 6000 Operating Instructions for values Twelve special read only points can be used for checking if the value actually cha...

Page 26: ...s been given a coast to stop command 28 CMD COAST Commands drive to make motor coast to a stop 29 DAY NIGHT Selects day or night mode Has no effect on drive operation 30 CURRENT LIM Sets maximum drive...

Page 27: ...er 415 73 BUS FB 1 Supplies feedback value for bus feedback 1 in percent 74 BUS FB 2 Supplies feedback value for bus feedback 2 in percent 75 AUTO RAMP Displays when drive deceleration rate is extende...

Reviews: