Technical data, mains supply 3 x 525-600 V
According to international requirements
VLT type 6002
6003
6004 6005 6006
6008 6011
Output current I
VLT,N
[A] (550 V)
2.6
2.9
4.1
5.2
6.4
9.5
11.5
I
VLT, MAX
(60 s) [A] (550V) 2.9
3.2
4.5
5.7
7.0
10.5
12.7
I
VLT,N
[A] (575 V) 2.4
2.7
3.9
4.9
6.1
9.0
11.0
I
VLT, MAX
(60 s) [A] (575 V) 2.6
3.0
4.3
5.4
6.7
9.9
12.1
Output S
VLT,N
[kVA] (550 V)
2.5
2.8
3.9
5.0
6.1
9.0
11.0
S
VLT,N
[kVA] (575 V) 2.4
2.7
3.9
4.9
6.1
9.0
11.0
Typical shaft output P
VLT,N
[kW]
1.1
1.5
2.2
3
4
5.5
7.5
Typical shaft output P
VLT,N
[HP]
1.5
2
3
4
5
7.5
10
Max. copper cable cross-section to motor and load-
sharing
[mm
2
] 4
4
4
4
4
4
4
[AWG]
2)
10
10
10
10
10
10
10
Rated Input
Current
I
VLT,N
[A] (550 V)
I
VLT,N
[A] (600 V)
2.5
2.2
2.8
2.5
4.0
3.6
5.1
4.6
6.2
5.7
9.2
8.4
11.2
10.3
Max.copper cable cross-section, power
[mm
2
] 4
4
4
4
4
4
4
[AWG]
2)
10
10
10
10
10
10
10
Max. prefuses (mains)
1)
[ - ]/UL [A]
3
4
5
6
8
10
15
Efficiency
0.96
Weight IP20 /
NEMA 1
[kg]
[Ibs]
10.5
23
10.5
23
10.5
23
10.5
23
10.5
23
10.5
23
10.5
23
Estimated power loss at max. load (550 V) [W]
65
73
103
131
161
238
288
Estimated power loss at max. load (600V) [W]
63
71
102
129
160
236
288
Enclosure
IP 20/NEMA 1
1. For type of fuse, see section
Fuses
.
2. American Wire Gauge (AWG).
3. Min. cable cross-section is the smallest cable cross-section allowed to be fitted into the terminals to comply with IP20. Always
comply with national and local regulations on min. cable cross-section.
VLT
®
6000 HVAC Series
54
MG.61.B5.02 - VLT
®
is a registered Danfoss trademark