Unpacking and ordering a VLT frequency convert-
er
If you are in doubt as to which frequency converter you
have received and which options it contains, use the
following to find out.
Type code ordering number string
On the basis of your order, the frequency converter is
given an ordering number that can be seen from the
nameplate on the unit. The number may look as fol-
lows:
VLT-6008-H-T4-B20-R3-DL-F10-A00-C0
This means that the frequency converter ordered is a
VLT 6008 for three-phase mains voltage of 380-460 V
(T4) in Bookstyle enclosure IP 20 (B20). The hardware
variant is with integral RFI filter, classes A & B (R3).
The frequency converter features a control unit (DL)
with a PROFIBUS option card (F10). No option card
(A00) and no conformal coating (C0) Character no. 8
( H) indicates the application range of the unit: H =
HVAC.
IP 00: This enclosure is only available for the larger
power sizes of the VLT 6000 HVAC series. It is rec-
ommended for installation in standard cabinets.
IP 20 Bookstyle: This enclosure is designed for cabinet
installation. It takes up a minimum of space and can
be fitted side-by-side without installation of extra cool-
ing equipment.
IP 20/NEMA 1: This enclosure is used as standard en-
closure for VLT 6000 HVAC. It is ideal for cabinet
installation in areas where a high degree of protection
is required. This enclose also permits side-by-side in-
stallation.
IP 54: This enclosure can be fitted direct to the wall.
Cabinets are not required. IP 54 units can also be in-
stalled side-by-side.
Hardware variant
The units in the programme are available in the fol-
lowing hardware variants:
ST:
Standard unit with or without control unit. With-
out DC terminals, except for
VLT 6042-6062, 200-240 V
VLT 6016-6072, 525-600 V
SL:
Standard unit with DC terminals.
EX:
Extended unit with control unit, DC terminals,
connection of external 24 V DC supply for back-
up of control PCB.
DX: Extended unit with control unit, DC terminals,
built-in mains fuses and disconnector, connec-
tion of external 24 V DC supply for back-up of
control PCB.
PF:
Standard unit with 24 V DC supply for back-up
of control PCB and built-in main fuses. No DC
terminals.
PS:
Standard unit with 24 V DC supply for back-up
of control PCB. No DC terminals.
PD: Standard unit with 24 V DC supply for back-up
of control PCB, built-in main fuses and discon-
nect. No DC terminals.
RFI filter
Bookstyle units always come
with
an integral RFI fil-
ter that complies with EN 55011-B with 20 m
screened/armoured motor cable and EN 55011-A1
with 150 m screened/armoured motor cable. Units for
mains voltage of 240 V and a motor power of up to
and including 3.0 kW (VLT 6005) and units for a mains
voltage of 380-460 V and a motor power of up to 7.5
kW (VLT 6011) are always supplied with an integral
class A1 & B filter. Units for higher motor power than
these (3.0 and 7.5 kW, respectively) can be ordered
either with or without an RFI filter.
Control unit (keypad and display)
All types of units in the programme, except for IP21
VLT 6402-6602, 380-460 V, VLT 6502-6652, 525-600
V and IP 54 units, can be ordered either with or with-
out the control unit. IP 54 units always come
with
a
control unit. All types of units in the programme are
available with built-in application options including a
relay card with four relays or a cascade controller
card.
Conformal Coating
All types of units in the programme are available with
or without conformal coating of the PCB.
VLT 6402-6602, 380-460 V and VLT 6102-6652,
525-600 V are only available coated.
VLT
®
6000 HVAC Series
MG.61.B5.02 - VLT
®
is a registered Danfoss trademark
27