Service functions 600-631
This parameter group contains functions such as op-
erating data, data log and fault log.
It also has information on the nameplate data of the
frequency converter.
These service functions are very useful in connection
with operating and fault analysis in an installation.
600-605 Operating data
Value:
Parameter
no.
Description
Operating data:
Display text
Unit
Range
600
Operating hours
(OPERATING HOURS)
Hours
0 - 130,000.0
601
Hours run
(RUNNING HOURS)
Hours
0 - 130,000.0
602
kWh counter
(KWH COUNTER)
kWh
-
603
No. of cut-ins
(POWER UP‘S)
Nos.
0 - 9999
604
No. of overtemps.
(OVER TEMP‘S)
Nos.
0 - 9999
605
No. of overvoltages
(OVER VOLT‘S)
Nos.
0 - 9999
Function:
These parameters can be read out via the serial com-
munication port, as well as via the display in the pa-
rameters.
Description of choice:
Parameter 600 Operating hours:
Gives the number of hours in which the frequency con-
verter has been in operation. The value is saved every
hour and when the power supply to the unit is cut off.
This value cannot be reset.
Parameter 601 Hours run:
Gives the number of hours in which the motor has been
in operation since being reset in parameter 619
Reset
of hours-run counter
. The value is saved every hour
and when the power supply to the unit is cut off.
Parameter 602 kWh counter:
Gives the output power of the frequency converter.
The calculation is based on the mean value in kWh
over one hour. This value can be reset using param-
eter 618
Reset of kWh counter
.
Parameter 603 No. of cut-ins:
Gives the number of cut-ins of supply voltage to the
frequency converter.
Parameter 604 No. of overtemps:
Gives the number of overtemperature errors on the
heat-sink of the frequency converter.
Parameter 605 No. of overvoltages:
Gives the number of overvoltages on the intermediate
circuit voltage of the frequency converter. The count is
only taken when Alarm 7
Overvoltage
is active.
VLT
®
6000 HVAC Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
176
MG.61.B5.02 - VLT
®
is a registered Danfoss trademark