23
MG.30.A7.02 - VLT
®
is a registered Danfoss trademark
Mains supply 3 x 200/220/230 V and 3 x 220/230/240 V
Technical data
According to international VDE and UL/CSA requirements
VLT type 3002 3003 3004 3006 3008 3011 3016 3022 3032 3042 3052
Constant torque (CT):
Output current
I
VLT,N
[A]
5.4
7.8 10.5
19.0 25.0 32.0 46.0 61.0 80.0 104.0 130.0
I
VLT,MAX
[A] (60 s)
6.7 12.5 17.0
30.0 40.0 51.2 73.6 97.6 120.0 156.0 195.0
Output
S
VLT,N
[kVA]
2.1
3.1
4.2
7.6 10.0 12.7 18.3 24.3 31.9 41.4 51.8
S
VLT,MAX
[kVA] (60 s)
2.7
4.9
6.7
12.0 15.9 20.4 29.2 38.9 47.8 62.1 77.7
Typical shaft output
P
VLT,N
[kW]
1.1
1.5
2.2
4.0
5.5
7.5 11.0 15.0 22.0 30.0 37.0
Quadratic torque (VT):
Output current
I
VLT,N
[A]
5.4
7.8 10.5
25.0 32.0 46.0 61.0 88.0 104.0 130.0 154.0
Output
S
VLT,N
[kVA]
1.9
2.9
4.0
10.0 12.7 18.3 24.3 35.1 41.4 51.8 61.3
Typical shaft output
P
VLT,N
[kW]
1.1
1.5
2.2
5.5
7.5 11,0 15,0 22.0 33.0 37.0 45.0
Max. cable cross-section
[mm
2
]
2.5
2.5
2.5
16.0 16.0 16.0 35.0 50.0 70.0 70.0 70.0
Max. motor cable length
[m]
300, with screened cables: 150 m
300
Output voltage
U
M
[%]
0-100, of mains voltage
max. 230 V
Output frequency
f
M
[Hz]
0-120 or 0-500; programmable
Rated motor voltage
U
M,N
[V]
200/220/230
Rated motor frequency
f
M,N
[Hz]
50/60/87/100
Thermal protection during operation
Integrated thermal motor protection (electronic);
thermistor to DIN 44081
Switching on output
Unlimited (frequent switching on output may result
in fault message)
Ramp times
[s]
0.1 - 3600
VLT type 3002 3003 3004 3006 3008 3011 3016 3022 3032 3042 3052
Max. input current
const. load I
L,N
[A]
6.8
9.1 13.3
17.5 22.2 26.4 41.7 52.2 78.0 102.0 128.0
quad. load I
L,N
[A]
6.8
9.1 13.3
23.1 29.6 42.0 56.8 72.3 102.0 128.0 152.0
Max. cable cross-section
[mm
2
]
2.5
2.5
2.5
16.0 16.0 16.0 35.0 50.0 120.0 120.0 120.0
Max. pre-fuses
1)
[A] 16.0 16.0 25.0
40.0 50.0 60.0 80.0 125.0 150.0 150.0 150.0
Supply voltage (VDE 0160)
[V]
3 x 200/220/230 ±10%
3 x 220/230/240
Supply frequency
[Hz]
50/60
Power factor / cos.
ϕ
1
0.9/1.0
Efficiency
0.96 at 100% load
Switching on input times/min.
times/min.
2
VLT type 3002 3003 3004 3006 3008 3011 3016 3022 3032 3042 3052
Weight (kg)
IP 00
7.4
7.4
7.4
-
-
-
-
-
-
-
-
IP 20
-
-
-
24.0 26.0 32.0 49.0 51.0
-
-
-
IP 21
8.0
8.0
8.0
-
-
-
-
- 143.0 145.0 147.0
IP 54 11.0 11.0 11.0
34.0 37.0 48.0 63.0 65.0 143.0 145.0 147.0
Power loss
CT [W] 60.0 100.0 130.0 270.0 425.0 399.0 615.0 935.0 760.0 910.0 1110
at max. load
VT [W] 60.0 100.0 130.0 425.0 580.0 651.0 929.0 1350 950.0 1110 1290
Enclosure
VLT type 3002-04: IP 00 / IP 21 / IP 54
VLT type 3006-22: IP 20 / IP 54
VLT type 3032-52: NEMA 1 / 2, IP 21 / 54
Vibration test
[g]
0.7
Relative humidity
[%]
VDE 0160 5.2.1.2.
Ambient temperature (to VDE 0160)
[°C]
VLT 3002-3004: -10
→
+40, operation at full load
2)
VLT 3006-3052: -10
→
+45/40(CT/VT) at full load
2)
[°C]
VLT 3002-3004: -30/25
→
+65/70, in storage/transport
VLT 3006-3052: -25
→
+65/70, in storage/transport
Frequency converter protection
Protection against earthing and short-circuiting
Emission
EN 55011, EN 55014
EMC standards
EN 50082-2, IEC 1000-4-2, IEC 1000-4-3, IEC 1000-4-4,
(See section “EMC test results”)
Immunity
IEC 1000-4-5
VDE 0160, ENV 50140, ENV 50141
+10%
+10%
+10%
+10%
+10%
-15%
-15%
-15%
-15%
-15%
1) VLT 3022: Only semi-conductor fuses; VLT 3032-3052: Bussman rapid type JJS built-in (see list)
2) In the range -10 to 0°C, the equipment can start and run; however, the display values and certain operating characteristics will not fulfil the
specifications.