MG.30.A7.02 - VLT
®
is a registered Danfoss trademark
200/230 V
3002 3003 3004 3006 3008 3011 3016 3022 3032 3042 3052
Factory settings
Parameter
103 Motor power
0.75
1.5
2.2
4
5.5
7.5
11
15
22
30
37
104 Motor voltage
200
200
200
200
200
200
200
200
230
230
230
105 Motor frequency
50
50
50
50
50
50
50
50
60
60
60
107 Motor current
3.8
7.8
10.0
17.2
25.0
32.0
46.0
57.2
80.0 104.0 130.0
108 Motor magnetizing current
2.4
3.2
4.6
6.8
8.8
10.0
14.4
21.6
28.8
27.1
37.4
109 Start voltage
21.3
20.2
19.3
19.4
19.5
19.4
19.4
19.5
22.3
21.9
22.2
110 Start compensation
4.2
2.10
1.86
0.79
0.50
0.35
0.21
0.11
0.00
0.00
0.00
111 U/F ratio
3.75
3.70
3.80
3.80
3.80
3.80
3.80
3.80
3.70
3.65
3.70
112 Slip compensation
4.6
2.56
2.80
1.60
2.00
1.90
1.80
1.66
0.75
0.37
0.42
113 Negative slip comp.
4.6
2.56
2.80
1.60
2.00
1.90
1.80
1.66
0.75
0.37
0.42
202 Max frequency
50
50
50
50
50
50
50
50
60
60
60
209 Current limit
6.7
12.5
17.0
30.0
40.0
51.2
73.6
97.6 120.0 156.0 195.0
215 Ramp-up time
1
1
1
10
10
10
10
10
30
30
30
216 Ramp-down time
1
1
1
10
10
10
10
10
30
30
30
217 Alt. ramp-up time
1
1
1
10
10
10
10
10
30
30
30
218 Alt. ramp-down time
1
1
1
10
10
10
10
10
30
30
30
232 Current, min. value
1.2
1.6
2.3
3.4
4.4
5.0
7.2
10.8
14.4
13.6
18.7
308 D.C. brake voltage
22
16
21
17
14
11
10
10
0.0
0.0
0.0
311 Trip delay at inverter fault
2
2
2
6
6
6
6
6
0
0
0