DANGER
SHOCK HAZARD FROM DC LINK OR EXTERNAL SOURCE
The terminal connections and the components of the drive can be live 5 minutes after the inverter is disconnected from the DC
supply and the motor has stopped. Also the load side of the inverter can generate voltage. A contact with this voltage can lead
to death or serious injury.
-
Before doing electrical work on the inverter:
•
Disconnect the inverter from the DC supply and make sure that the motor has stopped.
•
Lock out and tag out the power source to the inverter.
•
Make sure that no external source generates unintended voltage during work.
•
Wait 5 minutes before opening the cabinet door or the cover of the inverter.
•
Use a measuring device to make sure that there is no voltage.
WARNING
SHOCK HAZARD FROM INVERTER CONTROL TERMINALS
The control terminals can have a dangerous voltage also when the drive is disconnected from DC supply. A contact with this
voltage can lead to injury.
-
Make sure that there is no voltage in the control terminals before touching the control terminals.
WARNING
ACCIDENTAL MOTOR START
When there is a power-up, a power break, or a fault reset, the motor starts immediately if the start signal is active, unless the
pulse control for Start/Stop logic is selected. If the parameters, the applications or the software change, the I/O functions
(including the start inputs) can change. If you activate the auto reset function, the motor starts automatically after an automatic
fault reset. See the Application Guide. Failure to ensure that the motor, system, and any attached equipment are ready for start
can result in personal injury or equipment damage.
-
Disconnect the motor from the drive if an accidental start can be dangerous. Make sure that the equipment is safe to
operate under any condition.
WARNING
LEAKAGE CURRENT HAZARD
Leakage currents exceed 3.5 mA. Failure to ground the drive properly can result in death or serious injury.
-
Ensure the correct grounding of the equipment by a certified electrical installer.
WARNING
SHOCK HAZARD FROM PE CONDUCTOR
The drive can cause a DC current in the PE conductor. Failure to use a residual current-operated protective (RCD) device Type B
or a residual current-operated monitoring (RCM) device can lead to the RCD not providing the intended protection and
therefore can result in death or serious injury.
-
Use a type B RCD or RCM device on the mains side of the drive.
Safety
Operating Guide | VACON® NX Inverters FI4-FI8
AQ299433367205en-000101 / DPD00908
12 | Danfoss A/S © 2019.07
Summary of Contents for VACON NX FI6
Page 1: ...Operating Guide VACON NX Inverters FI4 FI8...
Page 2: ......