9.4.4 Motor Run Checklist
Context:
Do these checks before starting the motor.
Procedure
1.
Check that the motor is mounted properly and ensure that the machine connected to the motor allows the motor to be started.
2.
Set the maximum frequency reference (that is, the maximum speed of the motor) according to the motor and the device that is
connected to the motor.
3.
Before reversing the motor, make sure it can be done safely.
4.
Make sure that no power correction capacitors are connected to the motor cable.
5.
Make sure that the motor terminals are not connected mains potential.