12.10.42 Fault 9 - Undervoltage, Subcode S1 - DC-link too low during run
Cause
The DC-link voltage is lower than the limits.
•
Too low a supply voltage
•
AC drive internal fault
•
A defective input fuse
•
The external charge switch is not closed.
It is possible to set different responses in the application for this fault. See parameter group Protections.
Troubleshooting
•
If there is a temporary supply voltage break, reset the fault and start the drive again.
•
Do a check of the supply voltage. If the supply voltage is sufficient, there is an internal fault.
•
Ask instructions from the local distributor.
12.10.43 Fault 9 - Undervoltage, Subcode S2 - No data from power unit
Cause
The DC-link voltage is lower than the limits.
•
Too low a supply voltage
•
AC drive internal fault
•
a defective input fuse
•
the external charge switch is not closed.
It is possible to set different responses in the application for this fault. See parameter group Protections.
Troubleshooting
•
If there is a temporary supply voltage break, reset the fault and start the drive again.
•
Do a check of the supply voltage. If the supply voltage is sufficient, there is an internal fault.
•
Ask instructions from the local distributor.
12.10.44 Fault 9 - Undervoltage, Subcode S3 - Undervoltage control supervision
Cause
The DC-link voltage is lower than the limits.