Service Monitor User Manual
Danfoss Turbocor Compressors Inc.
19
ECD-00007M Rev. 1
Figure 19 General Data Page
Table 4 General Data Page Parameters
Parameter
Description
Ts [sat]
Saturated suction temperature
Tc [sat]
Saturated discharge temperature
3 Phase Power In
3-phase AC input power (mains input)
Shaft Speed
Actual shaft speed in RPM
Compressor Demand
Requested motor power demand as a percentage of maximum motor
power [kW].
Discharge Pressure
The actual discharge gauge pressure at the compressor flange as
measured by the suction pressure transducer.
Discharge Temperature
The actual discharge temperature at the compressor flange as
measured by the suction temperature/pressure transducer.
Suction Temperature
The actual suction temperature at the compressor flange as measured
by the suction temperature/pressure transducer.
Suction Pressure
The actual suction pressure at the compressor flange as measured by
the suction pressure transducer.
IGV % Open
% of Inlet guide vane opening, 0.0% means the vanes are at 90º to the
pipe line (Fully closed). 110% means 10º over turned from fully open.
Fault Text Box
Displays the compressor’s most recent active critical fault. Refer to
6.3.2 "Compressor Faults/Alarms" for fault details.
Alarm Text Box
Displays the compressor’s most recent active alarm. Refer to 6.3.2
"Compressor Faults/Alarms" for alarm details.
Interlock Status
Displays the status of the interlock: either open or closed.